2010-03-26 14:54:40 | *****DENIED***** |
| |
| THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE |
| BEEN ADDRESSED HOWEVER, BASED ON THE NEW INFORMATION |
| SUBMITTED, ADDRESS THE FOLLOWING COMMENTS AS REFERENCED |
| IN NFPA 101, LIFE SAFETY CODE, FLORIDA 2007 EDITION: |
| |
| 1. PLEASE EXPLAIN THE INCREASE IN OCCUPANT LOAD FIRST |
| SUBMITTED AT 218 IS NOW LISTED AS 336 PERSONS. BE |
| ADVISED THAT: IN BOTH NEW ASSEMBLY OCCUPANCIES (CHAPTER |
| 12 - 12.3.4.1) AND EXISTING ASSEMBLY OCCUPANCIES |
| (CHAPTER 13 - 13.3.4.1) WITH OCCUPANT LOADS MORE THAN |
| 300, THE OCCUPANCY SHALL BE PROVIDED WITH AN APPROVED |
| FIRE ALARM SYSTEM, UNLESS OTHERWISE PERMITTED BY |
| CERTAIN CRITERIA. |
| |
| 2. THE RESUBMITTED PLAN NOW REFERS TO DINING AREA 3 AS |
| LOUNGE/DANCE 70 SEATS (LOAD 115 PERSONS) SHOWING A DJ |
| BOOTH IN THE SOUTH CORNER OF THE ROOM. BE ADVISED THAT: |
| WHERE THE OCCUPANT LOAD EXCEEDS 100 (NEW ASSEMBLY, |
| CHAPTER 12 - 12.3.5.1) OR WHERE THE OCCUPANT LOAD |
| EXCEEDS 300 (EXISTING ASSEMBLY - 13.3.5.1), THE |
| FOLLOWING ASSEMBLY OCCUPANTS SHALL BE PROTECTED |
| THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| SPRINKLER SYSTEM: (1) DANCE HALLS (2) DISCOTHEQUES (3) |
| NIGHTCLUBS OR SIMILAR USAGE (4) ASSEMBLY OCCUPANCIES |
| WITH FESTIVAL SEATING |
| |
| 3. ASSEMBLY OCCUPANCIES SHALL BE PROVIDED WITH A |
| MINIMUM OF ONE TRAINED CROWD MANAGER OR CROWD MANAGER |
| SUPERVISOR. WHERE THE OCCUPANT LOAD EXCEED 250, |
| ADDITIONAL TRAINED CROWD MANAGERS OR CROWD MANAGER |
| SUPERVISORS SHALL BE PROVIDED AT A RATIO OF 1 FOR EVERY |
| 250 OCCUPANTS, UNLESS OTHERWISE PERMITTED AS PER |
| 12.7.6.1 OF NFPA 101 - LIFE SAFETY CODE. THE CROWD |
| MANAGER SHALL RECEIVE APPROVED TRAINNG IN CROWD CONTROL |
| MANAGEMENT TECHNIQUES. |
| |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |