2010-03-16 13:33:23 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. PLEASE REVISE PLAN TO INCLUDE OCCUPANT LOAD BASED ON |
| NEW SEATING PLAN FBC1004. |
| |
| 2. SHOW LIFE SAFETY INFORMATION; EXIT ACCESS TRAVEL |
| DISTANCE, REQUIRED WIDTH FOR EXITS BASED ON NEW |
| OCCUPANT LOAD, FBC 10. |
| |
| 3. PROVIDE A DETAIL FOR ACCESSIBLE SEATING AND SHOW |
| COMPLIANCE WITH FBC11-5.1 (5%), FBC11-4.32. NO |
| DIMENSIONS PROVIDED ON THE PLAN. FOR FIXED SEATING, SEE |
| FBC11-4.32 AND SHOW CLEAR FLOOR SPACE, AISLE WIDTH, |
| KNEE CLEARANCE, HEIGHT. |
| |
| 4. FBC11-5.2, A "HANDICAP BAR" IS SHOWN ON THE PLAN, |
| FBC11-4.32.4, BAR IS SHOWN AT 36", MAX 34" PERMITTED. |
| PLEASE REVISE. |
| |
| 5. BOND BREAK REQUIRED FOR STUCCO OVER WOOD SHEATHING |
| FBC1404.2.1. |
| |
| 6. PLAN IS NOT CLEAR. IS THE "VESTIBULE" (ENTRY TOWER) |
| EXISTING INTERIOR SPACE? PLAN STATES THAT THE ENTRY IS |
| TO RECEIVE A "NEW CEMENTITIOUS FINISH" OVER EXISTING |
| PLYWOOD. PLAN ALSO STATES "PROVIDE STUCCO FINISH ON |
| HIGH RIB LATH OVER NEW SOFFIT" BUT NO DETAIL/WIND |
| DESIGN CRITERIA PROVIDED FOR THE "NEW SOFFIT," FBC1609, |
| FBC*106. EXISTING CONDITIONS NOT CLEAR. FBC*106. |
| |
| |
| |
| |