2010-03-16 13:33:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE REVISE PLAN TO INCLUDE OCCUPANT LOAD BASED ON
 NEW SEATING PLAN FBC1004.
  
 2. SHOW LIFE SAFETY INFORMATION; EXIT ACCESS TRAVEL
 DISTANCE, REQUIRED WIDTH FOR EXITS BASED ON NEW
 OCCUPANT LOAD, FBC 10.
  
 3. PROVIDE A DETAIL FOR ACCESSIBLE SEATING AND SHOW
 COMPLIANCE WITH FBC11-5.1 (5%), FBC11-4.32. NO
 DIMENSIONS PROVIDED ON THE PLAN. FOR FIXED SEATING, SEE
 FBC11-4.32 AND SHOW CLEAR FLOOR SPACE, AISLE WIDTH,
 KNEE CLEARANCE, HEIGHT.
  
 4. FBC11-5.2, A "HANDICAP BAR" IS SHOWN ON THE PLAN,
 FBC11-4.32.4, BAR IS SHOWN AT 36", MAX 34" PERMITTED.
 PLEASE REVISE.
  
 5. BOND BREAK REQUIRED FOR STUCCO OVER WOOD SHEATHING
 FBC1404.2.1.
  
 6. PLAN IS NOT CLEAR. IS THE "VESTIBULE" (ENTRY TOWER)
 EXISTING INTERIOR SPACE? PLAN STATES THAT THE ENTRY IS
 TO RECEIVE A "NEW CEMENTITIOUS FINISH" OVER EXISTING
 PLYWOOD. PLAN ALSO STATES "PROVIDE STUCCO FINISH ON
 HIGH RIB LATH OVER NEW SOFFIT" BUT NO DETAIL/WIND
 DESIGN CRITERIA PROVIDED FOR THE "NEW SOFFIT," FBC1609,
 FBC*106. EXISTING CONDITIONS NOT CLEAR. FBC*106.
  
  
  
  