Plan Review Notes For Permit 10030180 |
Permit Number |
10030180 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-06 09:45:57 | 3700 SOUTH DIXIE HIGHWAY | | 10030180 | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 2. DEBRIS REMOVED THE SITE DAILY. | | | | 3. EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED. | | | | 4. ONLY ONE EMERGENCY LIGHT SHOWN ON PAGE E-2 WHICH IS | | NOT LOCATED NEAR AN EXIT DOOR. | | | | 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. | | | | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD, | | DUCT, AND FIRE SUPPRESSION SYSTEM. | | | | 7. PLEASE INDICATE ON FLOOR PLAN WHERE DISABLED PERSONS | | WILL SIT. | | | | 8. OCCUPANT LOAD WILL BE DETERMINED BY THIS OFFICE. | | | | 9. ON PAGE A-3 THE TENANT DEMISING WALL APPEARS TO BE | | ONLY ONE HOUR FIRE RATED. PLEASE EXPLAIN RATIONALE. | | | | 10. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | WALLS AND CEILINGS. | | | | 11. WRONG BUILDING CODE REFERENCED ON PAGE E-2. SHOULD | | READ 2007 EDITION. | | | | 12. GAS INSTALLATIONS SHALL COMPLY WITH NFPA 54, THE | | NATIONAL FUEL GAS CODE. | | | | 13. PLEASE ILLUSTRATE ALL PORTABLE AND K FIRE | | EXTINGUISHERS. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|