Plan Review Notes
Plan Review Notes For Permit 10030180
Permit Number 10030180
Review Stop E
Sequence Number 1
Notes
Date Text
2010-04-16 07:45:42THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 (F)(4) NEC . INDICATE
 SAME ON PLANS.
  
 2} THERE IS A CONFLICT IN LOCATION FOR PANEL "A" ON
 SHEETS E-1 & E-2, CLARIFY THE INTENDED LOCATION.106.1.1
 FBC AS AMENDED.
  
 3} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2007 FBC, 2008 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
 SEE SPECIFICATIONS ON SHEET E-2
  
 4} INDICATE COMPLIANCE WITH CHAPTER 13 OF THE FLORIDA
 BLDG CODE. 13.415. SHOW TIME CLOCK AND OCCUPANCY
 SENSORS LOCATIONS ON THE PLAN. THIS CAN BE DEMONSTRATED
 ON THE PLANS INDICATING THE WATTAGES OF THE LUMINAIRES
 CHOSEN FOR THE PROJECT CONFORM TO THE DENSITY
 REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE SCHEDULE
 TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 5} 210.62 SHOW WINDOWS.
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED
 WITHIN 450 MM (18 IN.) OF THE TOP OF A SHOW WINDOW FOR
 EACH 3.7 LINEAR M (12 LINEAR FT) OR MAJOR FRACTION
 THEREOF OF SHOW WINDOW AREA MEASURED HORIZONTALLY AT
 ITS MAXIMUM WIDTH. INDICATE LOCATION AND ON PANEL
 SCHEDULE.
  
 6} PER 220.14 (G) SHOW WINDOWS. SHOW WINDOWS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER OF THE FOLLOWING:
 (1) THE UNIT LOAD PER OUTLET AS REQUIRED IN OTHER
 PROVISIONS OF THIS SECTION
 (2) AT 200 VOLT-AMPERES PER 300 MM (1 FT) OF SHOW
 WINDOW
  
 7} 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION.
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  