2010-04-16 07:45:42 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 |
| NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING |
| |
| 1} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 |
| (2003), AND CIRCUITED PER 700.12 (F)(4) NEC . INDICATE |
| SAME ON PLANS. |
| |
| 2} THERE IS A CONFLICT IN LOCATION FOR PANEL "A" ON |
| SHEETS E-1 & E-2, CLARIFY THE INTENDED LOCATION.106.1.1 |
| FBC AS AMENDED. |
| |
| 3} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| DESIGNED UNDER. 2007 FBC, 2008 NEC ETC. ADD TO NOTES |
| FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 |
| FBC AS AMENDED. |
| SEE SPECIFICATIONS ON SHEET E-2 |
| |
| 4} INDICATE COMPLIANCE WITH CHAPTER 13 OF THE FLORIDA |
| BLDG CODE. 13.415. SHOW TIME CLOCK AND OCCUPANCY |
| SENSORS LOCATIONS ON THE PLAN. THIS CAN BE DEMONSTRATED |
| ON THE PLANS INDICATING THE WATTAGES OF THE LUMINAIRES |
| CHOSEN FOR THE PROJECT CONFORM TO THE DENSITY |
| REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE SCHEDULE |
| TO CORRELATE WITH THE ONES IN THE CALCULATIONS. |
| |
| 5} 210.62 SHOW WINDOWS. |
| AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED |
| WITHIN 450 MM (18 IN.) OF THE TOP OF A SHOW WINDOW FOR |
| EACH 3.7 LINEAR M (12 LINEAR FT) OR MAJOR FRACTION |
| THEREOF OF SHOW WINDOW AREA MEASURED HORIZONTALLY AT |
| ITS MAXIMUM WIDTH. INDICATE LOCATION AND ON PANEL |
| SCHEDULE. |
| |
| 6} PER 220.14 (G) SHOW WINDOWS. SHOW WINDOWS SHALL BE |
| CALCULATED IN ACCORDANCE WITH EITHER OF THE FOLLOWING: |
| (1) THE UNIT LOAD PER OUTLET AS REQUIRED IN OTHER |
| PROVISIONS OF THIS SECTION |
| (2) AT 200 VOLT-AMPERES PER 300 MM (1 FT) OF SHOW |
| WINDOW |
| |
| 7} 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. |
| EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| DISTINGUISHED FROM ALL OTHERS. |
| |