2010-03-24 14:14:07 | BUILDING PLAN REVIEW |
| PERMIT: 10030180 |
| ADD: 3700 S DIXIE HWY |
| CONT: MTC REMODELING, INC |
| TEL: (561)719-0725 |
| |
| DESIGNER: WILLIAM WATERS AA |
| PHONE: 561-307-5152 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLANS A3 INDICATE THE INSTALATION OF TWO NEW |
| EXTERIOR EXIT DOORS. PLANS FAIL TO PROVIDE THE WIND |
| DESIGN CRITERIA FOR THIS LOCATION.1603.1.4 WIND DESIGN |
| DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1.1 BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| |
| 1.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| |
| 1.3 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| |
| 1.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| |
| |
| 1.5 COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| |
| 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| DESIGNED. 2007 FBC & 2007 EXISTING BUILDING CODE, |
| CHAPTER 7, LEVEL 2 ALTERATIONS AND CHAPTER 9 CHANGE OF |
| OCCUPANCY. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5 |
| TABLE 503. |
| D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| E) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| BUILDING PERMIT |
| |
| 3) SHEET A-3 DOOR# 101& 102. EXISSTING BILDING CODE |
| 606.4 REPLACEMENT OF WINDOWS AND DOORS. THE REPLACEMENT |
| OF GARAGE DOORS, EXTERIOR DOORS, SKYLIGHTS, OPERATIVE |
| AND INOPERATIVE WINDOWS SHALL BE DESIGNED AND |
| CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF THE FLORIDA |
| BUILDING CODE, BUILDING . |
| FBC-B 1609.1.2 PROTECTION OF OPENINGS. IN WIND-BORNE |
| DEBRIS REGIONS, GLAZING IN BUILDINGS SHALL BE IMPACT |
| RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT |
| COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E |
| 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE DOORS |
| AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND 203 |
| OR AAMA 506 REFERENCED THEREIN AS FOLLOWS: |
| 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9144 MM) OF |
| GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE |
| TEST. |
| |
| THE PRODUCT APPROVALS SUBMITTED INDICATE THEY DO NOT |
| HAVE LARGE MISSILE IMPACT TESTING, STORM SHUTTERS OR |
| PANELS HAVING BEEN TESTED FOR LARGE MISSILE IMPACT |
| RATINGWOULD BE REQUIRED IF THESE APPROVALS ARE TO BE |
| INCLUDED WWITHIN THIS PERMIT. |
| |
| 4) RESTROOMS A-5 INDICATES THE RESTROOM WALLS ARE TO BE |
| PAINTED, PLEASE REVIEW FBC-B 1210.2. |
| |
| 5) A-5 FINISH SCHEDULE HAS NO INFORMATION FOR |
| COMPLIANCE WITH : 803.1 GENERAL. INTERIOR WALL AND |
| CEILING FINISHES SHALL BE CLASSIFIED IN ACCORDANCE WITH |
| ASTM E 84. SUCH INTERIOR FINISH MATERIALS SHALL BE |
| GROUPED IN THE FOLLOWING CLASSES IN ACCORDANCE WITH |
| THEIR FLAME SPREAD AND SMOKE-DEVELOPED INDEXES. |
| |
| CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450. |
| |
| CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450. |
| |
| CLASS C: FLAME SPREAD 76-200; SMOKE-DEVELOPED 0-450. |
| TABLE 803.5. |
| |
| 6) A-5 DOOR SCHEDULE DOOR 101 & 102 ARE INDICATED AS 44 |
| INCHES WIDE. PLEASE REVIEW THE NOA 05-1012.05 SHEET 1 |
| OF 9 INDICATES THE MAXIMUM DOOR WIDTH OF 36". |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 7) A3 NOTES DEALING WITH ROOM 102 DESERTS IS NOT CLEAR |
| IF THIS AREA IS FOR THE PUBLIC AS A SERVICE LINE OR |
| WILL THIS BE FOR THE EMPLOYEES ONLY. 11-5.5FOOD SERVICE |
| LINES SHALL HAVE A MINIMUM CLEAR WIDTH OF 36 INCHES |
| (915 MM), WITH A PREFERRED CLEAR WIDTH OF 42 INCHES |
| (1065 MM) TO ALLOW PASSAGE AROUND A PERSON USING A |
| WHEELCHAIR. TRAY SLIDES SHALL BE MOUNTED NO HIGHER THAN |
| 34 INCHES (865 MM) ABOVE THE FLOOR (SEE FIGURE 53). IF |
| SELF-SERVICE SHELVES ARE PROVIDED, AT LEAST 50 PERCENT |
| OF EACH TYPE MUST BE WITHIN REACH RANGES SPECIFIED IN |
| SECTIONS 11-4.2.5 AND 11-4.2.6. |
| |
| 11-5.6 TABLEWARE AND CONDIMENT AREAS. SELF-SERVICE |
| SHELVES AND DISPENSING DEVICES FOR TABLEWARE, DISHWARE, |
| CONDIMENTS, FOOD AND BEVERAGES SHALL BE INSTALLED TO |
| COMPLY WITH SECTION 11-4.2 (SEE FIGURE 54). |
| |
| 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |