Plan Review Notes For Permit 10030156 |
Permit Number |
10030156 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-03-25 11:24:52 | *****PARTIAL APPROVAL W/REMINDER***** | | | | PLANS APPEAR TO BE CODE COMPLIANT (WITH REMINDER); | | HOWEVER, RESUBMITTED PLANS TO BE SIGNED AND SEALED BY | | ENGINEER OF RECORD AS PER ORIGINALLY SUBMITTED SET. | | | | REMINDER: | | 1) THE MAXIMUM UNSUPPORTED ARMOVER LENGTH SHALL NOT | | EXCEED 12-INCHES WHEN SYSTEM PRESSURES EXCEED 100 PSI. | | REVISE ARMOVER DETAIL NOTES. (REFERENCE NFPA 13, 2007 | | EDITION, SECTION 9.2.3.5.2.1) | | 2) ENSURE PLANAGRAM ROOM #147 STORAGE HEIGHT DOES NOT | | EXCEED 8 FEET OR SPRINKLER DENSITY WILL NEED TO BE | | REVISED. | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|