2010-03-25 11:24:52*****PARTIAL APPROVAL W/REMINDER*****
  
 PLANS APPEAR TO BE CODE COMPLIANT (WITH REMINDER);
 HOWEVER, RESUBMITTED PLANS TO BE SIGNED AND SEALED BY
 ENGINEER OF RECORD AS PER ORIGINALLY SUBMITTED SET.
  
 REMINDER:
 1) THE MAXIMUM UNSUPPORTED ARMOVER LENGTH SHALL NOT
 EXCEED 12-INCHES WHEN SYSTEM PRESSURES EXCEED 100 PSI.
 REVISE ARMOVER DETAIL NOTES. (REFERENCE NFPA 13, 2007
 EDITION, SECTION 9.2.3.5.2.1)
 2) ENSURE PLANAGRAM ROOM #147 STORAGE HEIGHT DOES NOT
 EXCEED 8 FEET OR SPRINKLER DENSITY WILL NEED TO BE
 REVISED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  