Plan Review Notes
Plan Review Notes For Permit 10030156
Permit Number 10030156
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-03-11 12:47:28*****DENIED*****
  
  
 FP SHEET 1 OF 3:
  
 1) PROVIDE RESULTS FROM AN ACTUAL FIRE HYDRANT FLOW
 TEST OR FIRE PUMP TEST. (REFERENCE NFPA 13, 2007
 EDITION, SECTION 22.2.1)
  
 2) THE MAXIMUM UNSUPPORTED ARMOVER LENGTH SHALL NOT
 EXCEED 12-INCHES WHEN SYSTEM PRESSURES EXCEED 100 PSI.
 (REFERENCE NFPA 13, 2007 EDITION, SECTION 9.2.3.5.2.1)
  
 3) ELEVATION DIFFERENCE OF 3'-6" BETWEEN TWO CEILINGS.
 PROVIDE SPRINKLER COVERAGE FOR CEILING POCKET IN ROOM
 #101 AND #158. (REFERENCE NFPA 13, 2007 EDITION,
 SECTION 8.6.7.2)
  
 4) HANGER ASSEMBLY SHALL BE OF THE TYPE THAT PREVENTS
 UPWARD MOVEMENT FOR END OF THE LINE SPRINKLERS AND
 ARMOVERS WHEN SYSTEM PRESSURES EXCEED 100 PSI.
 (REFERENCE NFPA 13, 2007 EDITION, SECTION 9.2.3.4.4.1
 AND SECTION 9.2.3.5.2.2)
  
 5) NEW TREE SYSTEM SUPPLIED FROM EXISTING GRID SYSTEM
 HAS NOT BEEN HYDRAULICALLY CALCULATED.
  
  
 FP SHEET 2 OF 3:
  
 1) SPRINKLER LEGEND HAS THE QUANTITY LISTED AS FOUR IN
 THE NEW ESFR TYPE SPRINKLERS. THE PLAN APPEARS TO SHOW
 SIX NEW ESFR TYPE SPRINKLERS.
  
 2) HYDRAULIC CALCULATIONS DO NOT SUPPORT MORE THAN
 SPRINKLERS ON 1-1/4" PIPING. SEVERAL BRANCH LINES
 OUTSIDE THE CALCULATED REMOTE AREA CONTAIN MORE THAN
 FOUR SPRINKLERS PER BRANCH LINE.
  
 3) THE HYDRAULICALLY REMOTE SPRINKLER USED IN THE
 CALCULATION IS BASED UPON 168 SQUARE FEET. PROVIDE
 HYDRAULIC CALCULATIONS SUPPORTING THE SPRINKLERS THAT
 ARE PROTECTING AN AREA GREATER THAN 168 SQUARE FEET.
  
 4) "DESIGN AREA NO.1" INFORMATION BOX SHOWS A REQUIRED
 PRESSURE OF 16.5 PSI. THIS INFORMATION CONFLICTS WITH
 THE HYDRAULIC CALCULATION INFORMATION.
  
 5) BORDERED NOTE FOR LIGHT HAZARD OCCUPANCY STATES,
 "MAXIMUM STORAGE HEIGHT OF 12'-0"." PILED STORAGE IS
 NOT ALLOWED IN LIGHT HAZARD OCCUPANCIES. STORAGE
 HEIGHTS OF 12'-0" CORRESPOND TO AN OCCUPANCY OF
 ORDINARY HAZARD GROUP 2 WITH A MINIMUM DESIGN DENSITY
 OF 0.15 GPM/SQ. FT. (REFERENCE NFPA 13, 2007 EDITION,
 SECTION 5.3.2)
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  