Plan Review Notes
Plan Review Notes For Permit 10030118
Permit Number 10030118
Review Stop B
Sequence Number 2
Notes
Date Text
2010-03-22 14:04:18****PROVISO****
 ****PROVIDE AT INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE CANOPY FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 3. FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
  