2010-03-29 13:49:15 | | | | | 527-22ND STREET | | | | 1. NEW DOORS FOR APARTMENTS SHALL BE AT LEAST 20 MINUTE | | FIRE RATED. "DOORS THAT OPEN ONTO EXIT ACCESS | | CORRIDORS, OTHER THAN THOSE COMPLYING WITH 8.3.4 OR IN | | BUILDINGS MEETING 31.3.6.2 SHALL HAVE NOT LESS THAN A | | 20 MINUTE FIRE PROTECTION RATING IN ACCORDANCE WITH | | SECTION 8.3. RE: FFPC SECTION 31.3.6.2.1 (NFPA 101, | | 2006 EDITION.) | | | | 2. BUILDINGS ARE NOT OPTION 3 WITH FIRE SPRINKLERS IN | | SELECTED AREAS OR OPTION 4 WITH COMPLETE FIRE SPRINKLER | | SYSTEMS. | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | (561) 804-4724 PHONE | | (561) 804-4774 FAX |
|