Plan Review Notes
Plan Review Notes For Permit 10030097
Permit Number 10030097
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-03-29 13:42:15 
  
 545-21ST STREET
  
 1. NEW DOORS FOR THE APARTMENTS SHALL BE AT LEAST 20
 MINUTE FIRE RATED. "DOORS THAT OPEN ONTO EXIT ACCESS
 CORRIDORS, OTHER THAN THOSE COMPLYING WITH 8.3.4 OR IN
 BUILDINGS MEETING 31.3.6.2 SHALL HAVE NOT LESS THAN A
 20 MINUTE FIRE PROTECTION RATING IN ACCORDANCE WITH
 SECTION 8.3. RE: FFPC SECTION 31.3.6.2.1 (NFPA 101,
 2006 EDITION).
  
 2. BUILDINGS ARE NOT OPTION 3 WITH FIRE SPRINKLERS IN
 SELECTED AREAS OR OPTION 4 WITH COMPLETE FIRE SPRINKLER
 SYSTEMS.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved