2010-03-08 12:47:46 | |
| |
| REVISION DENIED/INCOMPLETE INFORMATION |
| |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} SHEET E-2 IS MISSING THE RISER DIAGRAM, ELECTRICAL |
| NOTES AND LEGEND, PANEL SCHEDULES AND LOAD |
| CALCULATIONS. ALSO THE PLUMBING DIAGRAM HAS BEEN |
| REMOVED, SUBMIT NEW PLUMBING PLANS TO SHOW THE |
| REVISIONS TO THE PLAN.105.1 FBC AS AMENDED. |
| |
| 2} POOL EQUIPMENT HAS BEEN ADDED, A SEPARATE POOL |
| PERMIT IS REQUIRED FOR THIS WORK, THE LOAD CALCULATIONS |
| AND PANEL SCHEDULE MUST BE REVISED. 105.1FBC. |
| |
| 3} THE METER LOCATION HAS BEEN REMOVED FROM SHEET E-1, |
| INDICATE LOCATION OF SAME SO THAT COMPLIANCE WITH |
| ARTICLES 225 AND 230 CAN BE REVIEWED. |
| |
| 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. THE AREA ON |
| EITHER SIDE OF THE RANGE DO NOT APPEAR TO COMPLY WITH |
| THE 2' SPACING. |
| |
| 5} THE PANEL INROOM 104 "LAUNDRY, 2ND FLOOR, IS IN |
| VIOLATION OF ARTICLE 110.26(A)(2) WIDTH OF WORKING |
| SPACE THE WIDTH OF THE WORKING SPACE IN FRONT OF THE |
| ELECTRIC EQUIPMENT SHALL BE THE WIDTH OF THE EQUIPMENT |
| OR 750 MM (30 IN.), WHICHEVER IS GREATER. IN ALL CASES, |
| THE WORK SPACE SHALL PERMIT AT LEAST A 90 DEGREE |
| OPENING OF EQUIPMENT DOORS OR HINGED PANELS.SEE SHEET |
| A-2 FOR DIMENSION OF THAT SPACE (2'-31/4") |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |