Plan Review Notes
Plan Review Notes For Permit 10030050
Permit Number 10030050
Review Stop B
Sequence Number 1
Notes
Date Text
2010-03-10 14:00:14REVISION DENIED
  
 1) THE ORIGINAL PLANS AND PERMIT WERE ISSUED UNDER THE
 2004 FBC W/2007 REVISIONS AND ASCE 7-02. THE REVISED
 DRAWINGS SPECIFY THE 2007 FBC AND ASCE 7-05. PLEASE
 CORRECT.
  
 2) THE REVISED PLANS DO NOT CORRESPOND TO THE ORDER OR
 NUMBERING OF THE APPROVED PLANS. IT APPEARS THAT YOUR
 INTENT IS TO SUBMIT ALL NEW DRAWINGS RATHER THAN SIMPLY
 REVISING THE APPROVED DRAWINGS. IF THIS IS THE CASE
 PLEASE SUBMIT TWO COMPLETE SETS OF ARCHITECTURAL AND
 STRUCTURAL DRAWINGS. NEW MECHANICAL AND PLUMBING
 DRAWINGS WILL ALSO BE REQUIRED.
  
 3) ON S3, THE MAXIMUM MEAN ROOF HEIGHT ( DISTANCE FROM
 FINISH GRADE TO MID POINT OF THE HIGHEST SLOPED ROOF)
 IS SPECIFIED AS 25' AND THE ACTUAL MEAN ROOF HEIGHT IS
 GREATER. PLEASE CORRECT.
  
 4) ON S3, THE WORST CASE COMPONENT AND CLADDING
 PRESSURE FOR THE TWO STORY STRUCTURE IN EXPOSURE 'C' IS
 SPECIFIED AS -57 PSF. THIS APPEARS TO BE TOO LOW.
 PLEASE SHOW HOW THIS WAS DETERMINED.
  
 5) THE EDGE PRESSURES ON S3 ARE BOTH SPECIFIED AS
 NEGATIVE. PLEASE CORRECT.
  
 6) THE NEW PLANS INDICATE THAT THE LIVING SPACE HAS
 BEEN INCREASED FROM THE APPROVED PLANS. PLANS WILL NEED
 TO BE REVIEWED BY PALM BEACH COUNTY TO DETERMINE IF
 ADDITIONAL IMPACT FEES ARE DUE.
  
 7) THE NEW PRODUCT APPROVALS ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD OF THE PROJECT.
  
 8) PRODUCT APPROVALS FOR SERIES 740 PROJECTED (AWNING)
 WINDOWS WAS SUBMITTED. THERE ARE NOT ANY OF THESE TYPE
 OF WINDOW SPECIFIED ON THE PLANS. PLEASE CLARIFY.
  
 9) THE PRODUCT APPROVALS FOR THE FRENCH DOORS (NO.
 07-0103.02) ARE EXPIRED. PLEASE SUBMIT CURRENT NOAS.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE ARCHED TOP WOOD
 FRONT DOOR (101) AND WOOD DOOR (102).
  
 11) SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION AND
 MAXIMUM DESIGN PRESSURE FOR THE TAMKO MODIFIED ROOF
 SYSTEM THAT WILL BE INSTALLED. PROVIDE ENHANCED
 FASTENING CALCULATIONS IF REQUIRED TO MEET ROOF
 UPLIFTS. SEE LIMITATION NUMBER 7 OF THE TAMKO PRODUCT
 APPROVAL.
  
 12) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/ PRODUCT EVALUATION FOR THE SPRAY FOAM
 INSULATION THAT WILL BE INSTALLED.
  
 13) SUBMIT REVISED ENERGY CALCULATIONS.
  
 14) PLEASE PROVIDE WRITTEN RESPONSES TO PLAN REVIEW
 COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]