Date |
Text |
2010-03-10 14:00:14 | REVISION DENIED |
| |
| 1) THE ORIGINAL PLANS AND PERMIT WERE ISSUED UNDER THE |
| 2004 FBC W/2007 REVISIONS AND ASCE 7-02. THE REVISED |
| DRAWINGS SPECIFY THE 2007 FBC AND ASCE 7-05. PLEASE |
| CORRECT. |
| |
| 2) THE REVISED PLANS DO NOT CORRESPOND TO THE ORDER OR |
| NUMBERING OF THE APPROVED PLANS. IT APPEARS THAT YOUR |
| INTENT IS TO SUBMIT ALL NEW DRAWINGS RATHER THAN SIMPLY |
| REVISING THE APPROVED DRAWINGS. IF THIS IS THE CASE |
| PLEASE SUBMIT TWO COMPLETE SETS OF ARCHITECTURAL AND |
| STRUCTURAL DRAWINGS. NEW MECHANICAL AND PLUMBING |
| DRAWINGS WILL ALSO BE REQUIRED. |
| |
| 3) ON S3, THE MAXIMUM MEAN ROOF HEIGHT ( DISTANCE FROM |
| FINISH GRADE TO MID POINT OF THE HIGHEST SLOPED ROOF) |
| IS SPECIFIED AS 25' AND THE ACTUAL MEAN ROOF HEIGHT IS |
| GREATER. PLEASE CORRECT. |
| |
| 4) ON S3, THE WORST CASE COMPONENT AND CLADDING |
| PRESSURE FOR THE TWO STORY STRUCTURE IN EXPOSURE 'C' IS |
| SPECIFIED AS -57 PSF. THIS APPEARS TO BE TOO LOW. |
| PLEASE SHOW HOW THIS WAS DETERMINED. |
| |
| 5) THE EDGE PRESSURES ON S3 ARE BOTH SPECIFIED AS |
| NEGATIVE. PLEASE CORRECT. |
| |
| 6) THE NEW PLANS INDICATE THAT THE LIVING SPACE HAS |
| BEEN INCREASED FROM THE APPROVED PLANS. PLANS WILL NEED |
| TO BE REVIEWED BY PALM BEACH COUNTY TO DETERMINE IF |
| ADDITIONAL IMPACT FEES ARE DUE. |
| |
| 7) THE NEW PRODUCT APPROVALS ARE REQUIRED TO BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD OF THE PROJECT. |
| |
| 8) PRODUCT APPROVALS FOR SERIES 740 PROJECTED (AWNING) |
| WINDOWS WAS SUBMITTED. THERE ARE NOT ANY OF THESE TYPE |
| OF WINDOW SPECIFIED ON THE PLANS. PLEASE CLARIFY. |
| |
| 9) THE PRODUCT APPROVALS FOR THE FRENCH DOORS (NO. |
| 07-0103.02) ARE EXPIRED. PLEASE SUBMIT CURRENT NOAS. |
| |
| 10) SUBMIT PRODUCT APPROVALS FOR THE ARCHED TOP WOOD |
| FRONT DOOR (101) AND WOOD DOOR (102). |
| |
| 11) SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION AND |
| MAXIMUM DESIGN PRESSURE FOR THE TAMKO MODIFIED ROOF |
| SYSTEM THAT WILL BE INSTALLED. PROVIDE ENHANCED |
| FASTENING CALCULATIONS IF REQUIRED TO MEET ROOF |
| UPLIFTS. SEE LIMITATION NUMBER 7 OF THE TAMKO PRODUCT |
| APPROVAL. |
| |
| 12) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS/ PRODUCT EVALUATION FOR THE SPRAY FOAM |
| INSULATION THAT WILL BE INSTALLED. |
| |
| 13) SUBMIT REVISED ENERGY CALCULATIONS. |
| |
| 14) PLEASE PROVIDE WRITTEN RESPONSES TO PLAN REVIEW |
| COMMENTS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |