2010-03-11 07:48:42SITE LANDSCAPING AND RE-STRIPING PARKING LOT
 PALM HARBOR MARINA
 400 NORTH FLAGLER DRIVE
  
 1. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY SECURITY
 GATES.
  
 2. A KNOX-BOX KEY SWITCH WILL BE REQUIRED TO OPEN ANY
 SECURITY FEATURES. PLEASE CONTACT WWW.KNOXBOX.COM TO
 ORDER KEY SWITCH.
  
 3. SUITABLE SIGNS SHALL BE PROVIDED ALONG THE BULKHEAD
 ADJACENT TO THE PAVER ROAD FOR A,B, AND C DOCKS "NO
 PARKING FIRE LANE BY ORDER OF THE POLICE AND FIRE
 DEPARTMENTS"
  
 4. AREAS THAT ARE MARKED FIRE LANE NO PARKING SHALL
 HAVE SUITABLE SIGNAGE.
  
 5. PLEASE CALL OUT ON THE PLANS THE MINIMUM 20 FEET
 REQUIRED FOR FIRE RESCUE ACCESS.
  
 6. FIRE HYDRANTS SHALL BE PROVIDED WITH A MINIMUM OF AT
 LEAST 7 1/2 FEET CLEARANCE TO THE FRONT AND SIDES AND A
 MINIMUM OF 4 FEET TO THE REAR.
  
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX