Plan Review Notes
Plan Review Notes For Permit 10030034
Permit Number 10030034
Review Stop M
Sequence Number 1
Notes
Date Text
2010-03-16 08:09:40PLAN DENIED
 1) NOTE PLANS SUBMITTED ARE REQUIRED TO BE SIGNED ,
 DATED AND SEALED BY THE DESIGNERS OF RECORD .
 2) PLEASE PROVIDE ENERGY CALCULATIONS AND LOAD
 CALCULATIONS WITH THE PLANS .
 3) PLEASE SUBMIT A COMPLETE SET OF MECHANICAL PLANS
 INCLUDING DUCT SIZE , EXHAUST DUCT , EXHAUST
 TERMINATION , FRESH AIR AND FRESH AIR CALCULATIONS .
 4) PLEASE PROVIDE A PIPING PLAN FOR SOLLAR PANELS ON
 THE ROOF .
 5) IN REGARDS TO PAGE M-103 OF THE PLANS PLEASE REFER
 TO SECTION 304.10 GUARDS . 2007 FBC (M)
 6) PLEASE REFER TO SECTION 306.5 EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES . 2007 FBC
 (M)
 7) PLEASE REFER TO SECTION 301.12 WIND RESISTANCE .
 2007 FBC (M)
 8) PLEASE REFER TO TABLE 1509.7 CLEARANCE BELOW RAISED
 ROOF MOUNTED MECHANICAL UNITS . 2007 FBC
 PLAN REVIEW BY HAROLD MOSER 561-805-6732