Plan Review Notes
Plan Review Notes For Permit 10030034
Permit Number 10030034
Review Stop E
Sequence Number 1
Notes
Date Text
2010-03-10 11:55:01DENIED **
  
 DRAWING DATE: 1/29/10 FOR FIRE STATION #5, EOC.
  
 1) NOTE: PLEASE OBTAIN LETTER/DOCUMENTATION FROM CITY
 ADMINISTRATION DECLARING THE USE OF THIS BUILDING. WILL
 IT BE USED FOR A CRITICAL OPERATIONS CENTER? WILL IT BE
 USED FOR ANY 911 SYSTEMS BACK UP?
 PLEASE SEE 2008 NFPA-70 708 FOR CRITICAL OPERATION
 POWER SYSTEMS AND WHETHER OR NOT BUILDING WILL BE
 DESIGNATED.
  
  
 2) NOTE: PLANS SUBMITTED ARE REQUIRED TO BE SIGNED,
 DATED AND SEALED BY THE DESIGNERS OF RECORD. PLANS
 SUBMITTED FOR EARLY REVIEW UNDER ( TO BE DETERMINED)
 *TBD*.
 PLEASE SEE FAC 61G15-23.002, FS 471.025
 THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENTS ARE MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 FOR DESIGN.
 2008 NFPA-70
 2003 NFPA-75
 2002 NFPA-72
 2006 NFPA-101
  
 4) NOTE: THERE WERE NO SUBMITTED FLORIDA ENERGY CODE
 FLA COM COMPLIANCE FORMS FOR ENERGY CODE REVIEW. PLEASE
 SEE FBC CHAPTER 13 AND BE SURE ALL COMPONENTS OF THE
 BUILDING/PLANS ARE IN THE INPUT DATA REPORT.
 PLEASE SEE 13-415.AB.5 FOR INTERIOR LIGHTING
 PERFORMANCE CALCULATIONS.
 PLEASE SEE 13-415.AB.2.2 FOR EXTERIOR LIGHTING
 PERFORMANCE CALCULATIONS.
 PLEASE SEE 13-400.A
  
 5) NOTE: * LIGHTNING PROTECTION SYSTEM NOTED ON PLANS
 PER NFPA-780 WILL BE UNDER SEPARATE PERMIT.
  
 6) NOTE: PLEASE SUBMIT COMPLETED PLANS. PLEASE COMPLETE
 ALL CIRCUITING AND COORDINATE WITH PANEL SCHEDULES.
 PANEL SCHEDULES ARE ACTUALLY BLANK. NO CIRCUITS, NO
 LOADS.
 LOADS FOR CIRCUITING, REQUIRED DEDICATED CIRCUITS AND
 LOADS CAN NOT BE REVIEWED AT THIS TIME.
 408.4,240,4,220,310.16.
 GIVEN AS GENERAL SECTIONS.
  
 7) NOTE: PLEASE SEE 2008 NEC FOR WET LOCATION
 RECEPTACLES.
  
 8) NOTE: PLEASE SEE 2008 NEC 250.94 FOR INTER-SYSTEM
 BOND.
  
 9) NOTE: PLEASE SEE 620 FOR REQUIRED DEDICATED CIRCUITS
 FOR ELEVATOR, PIT, MACHINE ROOM ETC.
 ** PLEASE BE SURE TO SEE STATE ELEVATOR CODE
 ASME-17.1-2004
  
 10) NOTE: PLEASE SUBMIT CUT/SPEC SHEETS FOR GENERATOR,
 ATS, FUEL TANK, UPS EQUIPMENT.
 ** CAN BE PART OF A PROVISO* FOR LATER DATE SUBMITTAL.
  
 11 NOTE: PLEASE COMPLETE LIGHTING FOR STAIRS (SEE
 1.12). PLEASE SHOW PHOTO-METRIC LEVELS FOR EGRESS
 STAIRS. PLEASE SEE NFPA-101 7.8.1.3, 7.9.1.2, .2.2.
  
 12) NOTE: WHEN USING OCCUPANCY SENSORS FOR EGRESS
 LIGHTING, PLEASE SEE FBC 1006.1.2, NFPA-101 7.8.1.2.2.
 ALL OCCUPANCY SENSORS CONTROLLING NORMAL AND EMERGENCY
 EGRESS LIGHTING IS REQUIRED TO BE *FAIL SAFE ON*.
  
 13) NOTE: SEE ROOM 3.23 AND STORAGE FOR 3.26. THE
 EQUIPMENT AS SHOWN APPEARS TO INTERFERE WITH REQUIRED
 CLEARANCES.
  
 14) NOTE: PLEASE SEE STORAGE ROOM 3.26 AND ANY OTHER
 SIMILAR LOCATIONS FOR MINIMUM LIGHTING CLEARANCES FOR
 FIXTURES. PLEASE SEE 410.11, 410.12.
  
 15) NOTE: PLEASE SEE FBC 13-415.AB.1.4 FOR EXTERIOR
 LIGHTING CONTROLS.
  
 16) NOTE: PLEASE SEE FBC 11-4.28,.1, .2 AND .3 FOR
 MINIMUM LEVELS, HEIGHTS AND LOCATIONS FOR ADA
 COMPLIANCE.
  
 17) NOTE: LOW VOLTAGE SYSTEMS WILL BE UNDER A SEPARTER
 PERMIT.
  
 18) NOTE: PLEASE SEE NEC 645 AND NFPA-75 FOR
 CONTRUCTION AND MINIMUM REQUIREMENTS FOR THE IT ROOMS.
  
  
 PLEASE SUBMIT COMPLETED PLANS. PLEASE CALL IF THERE ARE
 ANY QUESTIONS OR IF COMMENTS ARE NOT TYPED IN A CLEAR
 MANNER.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 HOURS: MONDAY THROUGH THURSDAY 8AM TO 5PM.
  