2010-03-10 11:55:01 | DENIED ** |
| |
| DRAWING DATE: 1/29/10 FOR FIRE STATION #5, EOC. |
| |
| 1) NOTE: PLEASE OBTAIN LETTER/DOCUMENTATION FROM CITY |
| ADMINISTRATION DECLARING THE USE OF THIS BUILDING. WILL |
| IT BE USED FOR A CRITICAL OPERATIONS CENTER? WILL IT BE |
| USED FOR ANY 911 SYSTEMS BACK UP? |
| PLEASE SEE 2008 NFPA-70 708 FOR CRITICAL OPERATION |
| POWER SYSTEMS AND WHETHER OR NOT BUILDING WILL BE |
| DESIGNATED. |
| |
| |
| 2) NOTE: PLANS SUBMITTED ARE REQUIRED TO BE SIGNED, |
| DATED AND SEALED BY THE DESIGNERS OF RECORD. PLANS |
| SUBMITTED FOR EARLY REVIEW UNDER ( TO BE DETERMINED) |
| *TBD*. |
| PLEASE SEE FAC 61G15-23.002, FS 471.025 |
| THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS |
| WHETHER OR NOT COMMENTS ARE MADE BY OTHER TRADES. |
| |
| 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| FOR DESIGN. |
| 2008 NFPA-70 |
| 2003 NFPA-75 |
| 2002 NFPA-72 |
| 2006 NFPA-101 |
| |
| 4) NOTE: THERE WERE NO SUBMITTED FLORIDA ENERGY CODE |
| FLA COM COMPLIANCE FORMS FOR ENERGY CODE REVIEW. PLEASE |
| SEE FBC CHAPTER 13 AND BE SURE ALL COMPONENTS OF THE |
| BUILDING/PLANS ARE IN THE INPUT DATA REPORT. |
| PLEASE SEE 13-415.AB.5 FOR INTERIOR LIGHTING |
| PERFORMANCE CALCULATIONS. |
| PLEASE SEE 13-415.AB.2.2 FOR EXTERIOR LIGHTING |
| PERFORMANCE CALCULATIONS. |
| PLEASE SEE 13-400.A |
| |
| 5) NOTE: * LIGHTNING PROTECTION SYSTEM NOTED ON PLANS |
| PER NFPA-780 WILL BE UNDER SEPARATE PERMIT. |
| |
| 6) NOTE: PLEASE SUBMIT COMPLETED PLANS. PLEASE COMPLETE |
| ALL CIRCUITING AND COORDINATE WITH PANEL SCHEDULES. |
| PANEL SCHEDULES ARE ACTUALLY BLANK. NO CIRCUITS, NO |
| LOADS. |
| LOADS FOR CIRCUITING, REQUIRED DEDICATED CIRCUITS AND |
| LOADS CAN NOT BE REVIEWED AT THIS TIME. |
| 408.4,240,4,220,310.16. |
| GIVEN AS GENERAL SECTIONS. |
| |
| 7) NOTE: PLEASE SEE 2008 NEC FOR WET LOCATION |
| RECEPTACLES. |
| |
| 8) NOTE: PLEASE SEE 2008 NEC 250.94 FOR INTER-SYSTEM |
| BOND. |
| |
| 9) NOTE: PLEASE SEE 620 FOR REQUIRED DEDICATED CIRCUITS |
| FOR ELEVATOR, PIT, MACHINE ROOM ETC. |
| ** PLEASE BE SURE TO SEE STATE ELEVATOR CODE |
| ASME-17.1-2004 |
| |
| 10) NOTE: PLEASE SUBMIT CUT/SPEC SHEETS FOR GENERATOR, |
| ATS, FUEL TANK, UPS EQUIPMENT. |
| ** CAN BE PART OF A PROVISO* FOR LATER DATE SUBMITTAL. |
| |
| 11 NOTE: PLEASE COMPLETE LIGHTING FOR STAIRS (SEE |
| 1.12). PLEASE SHOW PHOTO-METRIC LEVELS FOR EGRESS |
| STAIRS. PLEASE SEE NFPA-101 7.8.1.3, 7.9.1.2, .2.2. |
| |
| 12) NOTE: WHEN USING OCCUPANCY SENSORS FOR EGRESS |
| LIGHTING, PLEASE SEE FBC 1006.1.2, NFPA-101 7.8.1.2.2. |
| ALL OCCUPANCY SENSORS CONTROLLING NORMAL AND EMERGENCY |
| EGRESS LIGHTING IS REQUIRED TO BE *FAIL SAFE ON*. |
| |
| 13) NOTE: SEE ROOM 3.23 AND STORAGE FOR 3.26. THE |
| EQUIPMENT AS SHOWN APPEARS TO INTERFERE WITH REQUIRED |
| CLEARANCES. |
| |
| 14) NOTE: PLEASE SEE STORAGE ROOM 3.26 AND ANY OTHER |
| SIMILAR LOCATIONS FOR MINIMUM LIGHTING CLEARANCES FOR |
| FIXTURES. PLEASE SEE 410.11, 410.12. |
| |
| 15) NOTE: PLEASE SEE FBC 13-415.AB.1.4 FOR EXTERIOR |
| LIGHTING CONTROLS. |
| |
| 16) NOTE: PLEASE SEE FBC 11-4.28,.1, .2 AND .3 FOR |
| MINIMUM LEVELS, HEIGHTS AND LOCATIONS FOR ADA |
| COMPLIANCE. |
| |
| 17) NOTE: LOW VOLTAGE SYSTEMS WILL BE UNDER A SEPARTER |
| PERMIT. |
| |
| 18) NOTE: PLEASE SEE NEC 645 AND NFPA-75 FOR |
| CONTRUCTION AND MINIMUM REQUIREMENTS FOR THE IT ROOMS. |
| |
| |
| PLEASE SUBMIT COMPLETED PLANS. PLEASE CALL IF THERE ARE |
| ANY QUESTIONS OR IF COMMENTS ARE NOT TYPED IN A CLEAR |
| MANNER. |
| |