Plan Review Notes For Permit 10020578 |
Permit Number |
10020578 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-03-15 14:18:27 | 2007 FBC W/2009 REVISIONS | | COVERED PORCH ADDITION | | | | DENIED BY BUILDING | | | | 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY 'C' | | AND ON SHEET A4 OF THE PLANS EXPOSURE 'B' IS SPECIFIED. | | SEE THE 2009 REVISIONS TO 2004 FBC SECTION | | R301.2.1.4.3. | | | | 2) THE PLANS SPECIFY A 3:12 SLOPE FOR THE ROOF. FBC R | | 905.2.7 REQUIRES TWO LAYERS OF UNDERLAYMENT ON THE | | ROOF. PLEASE CORRECT NOTES. | | | | 3) FBC R803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE | | FASTENED WITH 8D RING SHANK NAILS. PLEASE CORRECT | | NOTES. | | | | 4) FBC R320.7 REQUIRES ROOF DOWNSPOUTS ARE REQUIRED TO | | DISCHARGE A MINIMUM OF 1 FOOT AWAY FROM THE STRUCTURE. | | PLEASE NOTE ON PLANS. | | | | 5) FBC R 703.6.3 REQUIRES A BOND BREAK BETWEEN THE | | WATER-RESISTIVE BARRIER AND THE STUCCO. SHOW | | COMPLIANCE. | | | | 6) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | GAF ROYAL SOVEREIGN SHINGLES ( NOA NO. 07-1012.02 ) | | HAVE BEEN SUPERSEDED BY NOA NO. 09-0825.06. PLEASE | | SUBMIT TWO COPIES OF THE CURRENT PRODUCT APPROVALS. DCA | | RULE 9B-72 | | | | 7) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND | | APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT. | | 106.3.3 CITY AMENDMENTS | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|