Notes |
Date |
Text |
2010-02-25 16:21:36 | PASSED WITH PROVISOS 02/25/2010: | | | | 1. EOR HAS REVISED PLAN RELATED TO SOIL DENSITY. | | 2. PIPE MATERIAL FOR STORM WORK IN THE BUILDING HAS | | BEEN IDENTFIED AS PVC. | | 3. SHOP DRAWINGS HAVE BEEN PROVIDED. | | (MANHOLE COVER AND FRAME MUST BE HINGE DESIGN AS SHOWN | | ON CWPB DETAIL ST-2) | | (SEE DETAIL ATTACHED) | | 4. CWPB STANDARD DETAILS HAVE BEEN ATTACHED ALONG WITH | | GENERAL NOTES. | | 5. EOR HAS INCLUDED CWPB DETAIL GS-2 IN AN EFFORT TO | | ILLUSTRATE PIPE TO MANHOLE CONNECTION. | | 6. 15" RCP STORM PIPE IN CONFLICT HAS ALSO BEEN SHOWN | | AND ELEVATION OF NEW 24" PVC PIPE WAS CHANGE TO AVOID | | CONFLICT. | | | | MANUEL JULIAN GONZALEZ | | ESD ENGINEERING REVIEW | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | | |
|