2010-02-25 11:56:21 | SHEET C-9: | | | | 1.NOTE 3 DENSITY SPECIFICATION FOR T-180 IS 98% | | 2.PIPE MATERIAL NOT APPROVED FOR PROPOSED USE. PER FBC | | PLUMBING CODE, SECTION 1102. | | 3.SHOP DRAWING, MATERIAL SUBMITTALS, AND SPECIFICATIONS | | REQUIRED. | | 4.PROVIDE STRUCTURE CONNECTION DETAIL FOR PIPE, RWL, | | AREA DRAINS, AND CONDENSATE LINES. | | | | MANUEL JULIAN GONZALEZ | | ESD ENGINEERING REVIEW | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING |
|