2010-02-25 11:56:21SHEET C-9:
  
 1.NOTE 3 DENSITY SPECIFICATION FOR T-180 IS 98%
 2.PIPE MATERIAL NOT APPROVED FOR PROPOSED USE. PER FBC
 PLUMBING CODE, SECTION 1102.
 3.SHOP DRAWING, MATERIAL SUBMITTALS, AND SPECIFICATIONS
 REQUIRED.
 4.PROVIDE STRUCTURE CONNECTION DETAIL FOR PIPE, RWL,
 AREA DRAINS, AND CONDENSATE LINES.
  