Date |
Text |
2010-03-09 08:58:40 | |
| BUILDING PLAN REVIEW |
| PERMIT: 10020540 |
| ADD: 2000 PALM BEACH LAKES 1ST FLOOR |
| CONT: ENGINEERED AIR LLC |
| TEL: (954) 974-7277 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). |
| |
| 1) MISSING THE WIND DESIGN CRITERIA: |
| FBC-BUILDING1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| |
| 1.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| |
| 1.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| |
| 1.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| |
| 1.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| |
| 2) FBC-BUILDING 1604.4 EVERY STRUCTURE SHALL BE |
| DESIGNED TO RESIST THE OVERTURNING EFFECTS CAUSED BY |
| LATERAL FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION |
| 1609 FOR WIND. |
| |
| 3) WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES |
| AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED |
| AND INSTALLED TO RESIST WIND PRESSURES ON THE EQUIPMENT |
| AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE |
| FLORIDA BUILDING CODE, BUILDING. |
| 301.12 FBC MECHANICAL/ 2007 |
| |
| 4) IT ROOM REQUIRES 1HR RATED WALLS PER 2008 |
| NEC645.4(5) |
| 2007 FBC 712.3.1 THROUGH PENETATIONS.R |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953. |
| |