Plan Review Notes
Plan Review Notes For Permit 10020520
Permit Number 10020520
Review Stop B
Sequence Number 1
Notes
Date Text
2010-02-23 16:05:26RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- GAF NOA 03-0501.02 SUBMITTED EXPIRED ON 11/06/08.
 NEED TO PROVIDE CURRENT NOA.
  
 2- IF NOA SUBMITTED REQUIRES SIGNED AND SEALED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS, THEN SIGNED AND SEALED CALCULATIONS NEED TO BE
 PROVIDED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712