2010-03-10 14:07:21 | RESIDENTIAL (R3) ADDITION/RENOVATION BUILDING REVIEW |
| CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- REVISE ENERGY CALCULATIONS: |
| A) NEED TO PROVIDE REVISED FORM FOR 2007 CODE. ONE |
| SUBMITTED IS FOR 2004 CODE. NOTE: THERE IS NOT FORM C |
| ON 2009 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE. |
| |
| B) CORRECT THE CLIMATE ZONE. THIS IS NOT ZONE 7. |
| |
| C) COORDINATE WALL TYPE AND INSULATION, CEILING TYPE |
| AND INSULATION WITH INFORMATION SHOWN ON PLANS. |
| |
| D) CLARIFY EXISTING COOLING SEER VALUE. CHECK PLANS AND |
| EXISTING UNIT. |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) SLIDING GLASS DOORS. NOA 07-0808.09 IS CLOSED |
| ACCORDING TO THE MIAMI-DADE WEBSITE. NEED TO PROVIDE |
| CURRENT NOA. |
| |
| B) ROOF SHINGLES. NOA 08-0414.01 IS SUPERSEDED |
| ACCORDING TO THE MIAMI-DADE WEBSITE. NEED TO PROVIDE |
| CURRENT NOA. |
| |
| C) STORM SHUTTERS. AND PROVIDE COMPLETE INSTALLATION |
| SCHEDULE AND CLEARLY MARK ON SHUTTERS DRAWING SPECIFIC |
| MOUNTING CONDITIONS AND FASTENER TYPE AND SPACING. |
| |
| 3- ENGINEER OF RECORD TO REVIEW AND APPROVE THESE |
| PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 4- PLANS NEED TO PROVIDE SPECIFICATIONS AND DETAILS |
| SHOWING HOW PROVIDING GARAGE SEPARATION AS REQUIRED BY |
| SEC. 309.2 OF 2007 FLORIDA RESIDENTIAL CODE. CEILING |
| AND WALLS NEED TO PROVIDE SUCH SEPARATION. |
| |
| 5- ESP LOW INSULATION: |
| A) ACCORDING TO THE NOTES AND WARNINGS ON INFORMATION |
| SUBMITTED NEED TO PROVIDE A PROPER THERMAL BARRIER IT |
| CAN'T BE EXPOSED. |
| |
| B) PROVIDE INFORMATION SHOWING HOW PROVIDING THE |
| R-VALUE REQUIRED BY THE ENERGY CALCULATIONS. |
| |
| 6- TRUSS PACKAGE IS MISSING THE TRUSS T-1 DRAWING. |
| ALSO, TRUSS LAYOUT AND INDIVIDUAL TRUSS DRAWINGS SHEETS |
| NEED TO HAVE ORIGINAL SEAL AND SIGNATURE OF THE TRUSS |
| ENGINEER. AND, PROVIDE TRUSS ENGINEER COMPLETE |
| INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| |
| 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| **NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| |
| 8- SHEET A-1: |
| A) SPECIFY SAFETY GLASS FOR MASTER BATHROOM WINDOW AS |
| REQUIRED BY SEC. R308.4(5) OF 2007 FLORIDA RESIDENTIAL |
| CODE. |
| |
| B) ENGINEERING CRITERIA INFORMATION: CLARIFY WHAT'S |
| BUILDING CATEGORY IIIB AND SPECIFY WHAT SECTION OF THE |
| CODE IS THIS TAKEN FROM. |
| |
| 9- OWES $1179.85 PERMIT FEE BALANCE. |
| |