2010-03-04 08:59:09DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS ENGINEERS SHALL LEGIBLY INDICATE THEIR
 ADDRESS IN THEIR TITLE BLOCK ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
  
 2. SHT 1 11-4.23.5 URINALS. IF URINALS ARE PROVIDED,
 THEN AT LEAST ONE SHALL COMPLY WITH SECTION 11-4.18.
 SHOW COMPLIANCE WITH THE FOLLOWING:
 11-4.18.2 HEIGHT. URINALS SHALL BE STALL-TYPE OR
 WALL-HUNG WITH AN ELONGATED RIM AT A MAXIMUM OF 17
 INCHES (430 MM) ABOVE THE FINISH FLOOR.
  
 11-4.18.3 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE 30
 INCHES BY 48 INCHES (760 MM BY 1220 MM) SHALL BE
 PROVIDED IN FRONT OF URINALS TO ALLOW FORWARD APPROACH.
 THIS CLEAR SPACE SHALL ADJOIN OR OVERLAP AN ACCESSIBLE
 ROUTE AND SHALL COMPLY WITH SECTION 11-4.2.4. URINAL
 SHIELDS THAT DO NOT EXTEND BEYOND THE FRONT EDGE OF THE
 URINAL RIM MAY BE PROVIDED WITH 29 INCHES (735 MM)
 CLEARANCE BETWEEN THEM.
  
 11-4.18.4 FLUSH CONTROLS. FLUSH CONTROLS SHALL BE HAND
 OPERATED OR AUTOMATIC, AND SHALL COMPLY WITH SECTION
 11-4.27.4, AND SHALL BE MOUNTED NO MORE THAN 44 INCHES
 (1120 MM) ABOVE THE FINISH FLOOR.
  
 11-4.18.4 FLUSH CONTROLS. FLUSH CONTROLS SHALL BE HAND
 OPERATED OR AUTOMATIC, AND SHALL COMPLY WITH SECTION
 11-4.27.4, AND SHALL BE MOUNTED NO MORE THAN 44 INCHES
 (1120 MM) ABOVE THE FINISH FLOOR.
  
 3. SHT 1 IF TOILET STALLS ARE PROVIDED, THEN AT LEAST
 ONE SHALL BE A STANDARD TOILET STALL COMPLYING WITH
 SECTION 11-4.17. SECTION 11-4.22.4. THE STANDARD
 ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN ACCESSIBLE
 LAVATORY WITHIN IT, THE SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN 19 INCHES WIDE BY 17 INCHES (483 MM BY 432
 MM) DEEP, NOMINAL SIZE, AND WALL MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 11-4.17. SEE FIGURE
 11-17(E).
  
 4. 11-4.22.6 LAVATORIES AND MIRRORS. IF LAVATORIES AND
 MIRRORS ARE PROVIDED, THEN AT LEAST ONE OF EACH SHALL
 COMPLY WITH SECTION 11-4.19. THERE ARE NO ACCESSIBLE
 LAVS INDICATED IN THE WOMEN'S TOILET ROOM. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 11-4.19 LAVATORIES AND MIRRORS.
  
 11-4.19.1 GENERAL. THE REQUIREMENTS OF SECTION 11-4.19
 SHALL APPLY TO LAVATORY FIXTURES, VANITIES, AND
 BUILT-IN LAVATORIES.
  
 11-4.19.2 HEIGHT AND CLEARANCES. LAVATORIES SHALL BE
 MOUNTED WITH THE RIM OR COUNTER SURFACE NO HIGHER THAN
 34 INCHES (865 MM) ABOVE THE FINISH FLOOR. PROVIDE A
 CLEARANCE OF AT LEAST 29 INCHES (735 MM) ABOVE THE
 FINISH FLOOR TO THE BOTTOM OF THE APRON. KNEE AND TOE
 CLEARANCE SHALL COMPLY WITH FIGURE 31.
  
 11-4.19.3 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE 30
 INCHES BY 48 INCHES (760 MM BY 1219 MM) COMPLYING WITH
 SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A
 LAVATORY TO ALLOW FORWARD APPROACH. SUCH CLEAR FLOOR
 SPACE SHALL ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH
 THE LAVATORY (SEE FIGURE 32).
  
 11-4.19.4 EXPOSED PIPES AND SURFACES. HOT WATER AND
 DRAIN PIPES UNDER LAVATORIES SHALL BE INSULATED OR
 OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT. THERE
 SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER
 LAVATORIES.
  
 11-4.19.5 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, AND
 ELECTRONICALLY CONTROLLED MECHANISMS ARE EXAMPLES OF
 ACCEPTABLE DESIGNS. IF SELF-CLOSING VALVES ARE USED THE
 FAUCET SHALL REMAIN OPEN FOR AT LEAST 10 SECONDS.
  
 5. SHT 2 THE EMPLOYEE LOUNGE SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH THE FOLLOWING:
 11-4.24 SINKS.
  
 11-4.24.1 GENERAL. SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.24.
  
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34 INCHES (865 MM) ABOVE
 THE FINISH FLOOR.
  
 11-4.24.3 KNEE CLEARANCE. KNEE CLEARANCE THAT IS AT
 LEAST 27 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE,
 AND 19 INCHES (485 MM) DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS.
  
 11-4.24.4 DEPTH. EACH SINK SHALL BE A MAXIMUM OF 61/2
 INCHES (165 MM) DEEP.
  
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK (SEE FIGURE 32). - NOTE: CABINET DOORS ARE NOT
 ALLOWED IN THE CLEAR FLOOR SPACE.
  
 11-4.24.6 EXPOSED PIPES AND SURFACES. HOT WATER AND
 DRAIN PIPES EXPOSED UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT AGAINST CONTACT.
 THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
  
 11-4.24.7 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE
 DESIGNS.
  
 6. SHT 4, A SANITARY ISOMETRIC RISER DIAGRAM IS
 REQUIRED SHOWING ALL PIPE SIZES, TRAPS & VENTS.
 SECTIONS 106.3.5.1.3(4)(6)(13), 701.1, 901.1 & 1001.1
  
 7. SHT 4, A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED
 SHOWING ALL PIPE SIZES, VALVES & (WHERE REQUIRED BY
 SECTION 604.9), WATER HAMMER ARRESTORS. SECTIONS
 106.3.5.1.3(3)(10)(13) & 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  