2010-03-04 20:28:42REVIEW #:
 ACTION:
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE VENTILATION CALCULATIONS FOR ALL
 RECONFIGURED SPACES IN ACCORDANCE WITH FBC-EB 709.1 AND
 FBC-M SECTION 403, INCLUDING NEW OFFICES AND EMPLOYEE
 LOUNGE.
  
 2. PROVIDE SIZE OF RETURN AIR TRANSFER DUCTS IN
 ACCORDANCE WITH FBC-M 601.4.
  
 3. PROVIDE EXHAUST FAN SCHEDULE SHOWING EXHAUST RATE
 CFM TO DEMONSTRATE COMPLIANCE WITH FBC-M SECTION 403.
  
  
  