2010-03-01 16:58:16 | ** DENIED ** |
| |
| |
| 1) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF |
| WORK SHOWN ON PLANS IS LOW. |
| PLEASE KNOW THAT PER FBC 108.3 THE APPLIED SCOPE OF |
| WORK IS TO INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, |
| DESIGN COST EVEN IF ANY OF THESE THINGS ARE OWNER |
| SUPPLIED. |
| |
| 2) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR NEW |
| AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. |
| 408.4,310.16,240.4, 220, 210 ETC |
| THE CIRCUITING ON PANEL SCHEDULES ARE NOT PERMITTED TO |
| BE GENERIC. * LIGHTING AND RECEPTACLES * IS NOT |
| ACCEPTABLE. PLEASE SEE CODE COMMENTARY IN THE NEC UNDER |
| 408.4. |
| |
| 3) NOTE: PLEASE PLACE NOTE ON PLANS FOR COMPUTER ROOM. |
| * NO NEC 645 WIRING METHODS PERMITTED* OR WORDS TO THAT |
| AFFECT. |
| THIS IS NOT AN IT ROOM BY DEFINITION BASED ON THE PLANS |
| SUBMITTED THEREFORE WIRING METHODS WHICH ARE LESS |
| STRINGENT IN 645 ARE NOT ALLOWED. |
| |
| 4) NOTE: PLEASE SEE FBC 13-415.AB.1.1, .1.2 AND .1.3 |
| FOR NEW LIGHTING CONTROLS. ANY NEW SEPARATE SPACES AND |
| NEW CONTROLS SHALL MEET MINIMUM PRESCRIPTIVE |
| REQUIREMENTS. |
| |
| 5) NOTE: PLANS INDICATE POWER FOR NEW EXHAUST FANS IN |
| BATHROOMS HOWEVER NO CONTROL LOCATIONS SHOWN. |
| PLEASE SEE MECHANICAL COMMENTS FOR FLORIDA MECHANICAL |
| CODE WHICH REQUIRES CONTROLS. |
| |
| 6) NOTE: PLEASE SEE 240.21, 408.36 AS A MAIN IS |
| REQUIRED ON THE SECONDARY SIDE OF THE TRANSFORMER. ALL |
| TAPPED CONDUCTORS SHALL TERMINATE IN OVER CURRENT |
| PROTECTION. |
| THIS IS A LIFE SAFETY AND FIRE HAZARD AND WILL BE |
| REQUIRED TO BE CORRECTED. |
| |
| 7) NOTE: LOADS ON SERVICE AND PANELS ARE TO BE |
| COMPLETED. PANELS DO NOT INDICATE LOADS. |
| 220, 220.14,220.12, 220.42, .43, ETC |
| PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125%. |
| |
| 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS FOR NEW BEING INSTALLED IN ADDITION TO |
| EXISTING IN NEW AREAS. |
| 13-415.AB.5 |
| |
| 6) NOTE: HOW IS PANEL LA FED? THERE IS NO OCP SHOWN IN |
| PANEL L FOR SUB PANEL. |
| SEE NOTE #6 ABOVE. |
| |
| 7) NOTE: COVER SHEET INDICATES SOME CODES FROM THE 2004 |
| FBC. PLEAS EBE SURE THE PLANS INDICATE THE FOLLOWING |
| FOR THIS REVIEWER FOR RELEVANT DESIGN. |
| |
| |
| 2007 FBC W/ 2009 SUPPLEMENTS |
| 2006 NFPA-101 |
| 2008 NFPA-70 |
| 2002 NFPA-728) NOTE: NO FIRE ALARM DEVICES, SYSTEMS |
| SHOWN. PLEASE SEE FBC 11-4.28.1,.2 AND .3 FOR MINIMUM |
| LOCATIONS, LEVELS AND HEIGHTS FOR ADA COMPLIANCE. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |