Plan Review Notes
Plan Review Notes For Permit 10020496
Permit Number 10020496
Review Stop E
Sequence Number 1
Notes
Date Text
2010-03-01 16:58:16** DENIED **
  
  
 1) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF
 WORK SHOWN ON PLANS IS LOW.
 PLEASE KNOW THAT PER FBC 108.3 THE APPLIED SCOPE OF
 WORK IS TO INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST EVEN IF ANY OF THESE THINGS ARE OWNER
 SUPPLIED.
  
 2) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR NEW
 AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULES.
 408.4,310.16,240.4, 220, 210 ETC
 THE CIRCUITING ON PANEL SCHEDULES ARE NOT PERMITTED TO
 BE GENERIC. * LIGHTING AND RECEPTACLES * IS NOT
 ACCEPTABLE. PLEASE SEE CODE COMMENTARY IN THE NEC UNDER
 408.4.
  
 3) NOTE: PLEASE PLACE NOTE ON PLANS FOR COMPUTER ROOM.
 * NO NEC 645 WIRING METHODS PERMITTED* OR WORDS TO THAT
 AFFECT.
 THIS IS NOT AN IT ROOM BY DEFINITION BASED ON THE PLANS
 SUBMITTED THEREFORE WIRING METHODS WHICH ARE LESS
 STRINGENT IN 645 ARE NOT ALLOWED.
  
 4) NOTE: PLEASE SEE FBC 13-415.AB.1.1, .1.2 AND .1.3
 FOR NEW LIGHTING CONTROLS. ANY NEW SEPARATE SPACES AND
 NEW CONTROLS SHALL MEET MINIMUM PRESCRIPTIVE
 REQUIREMENTS.
  
 5) NOTE: PLANS INDICATE POWER FOR NEW EXHAUST FANS IN
 BATHROOMS HOWEVER NO CONTROL LOCATIONS SHOWN.
 PLEASE SEE MECHANICAL COMMENTS FOR FLORIDA MECHANICAL
 CODE WHICH REQUIRES CONTROLS.
  
 6) NOTE: PLEASE SEE 240.21, 408.36 AS A MAIN IS
 REQUIRED ON THE SECONDARY SIDE OF THE TRANSFORMER. ALL
 TAPPED CONDUCTORS SHALL TERMINATE IN OVER CURRENT
 PROTECTION.
 THIS IS A LIFE SAFETY AND FIRE HAZARD AND WILL BE
 REQUIRED TO BE CORRECTED.
  
 7) NOTE: LOADS ON SERVICE AND PANELS ARE TO BE
 COMPLETED. PANELS DO NOT INDICATE LOADS.
 220, 220.14,220.12, 220.42, .43, ETC
 PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125%.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW BEING INSTALLED IN ADDITION TO
 EXISTING IN NEW AREAS.
 13-415.AB.5
  
 6) NOTE: HOW IS PANEL LA FED? THERE IS NO OCP SHOWN IN
 PANEL L FOR SUB PANEL.
 SEE NOTE #6 ABOVE.
  
 7) NOTE: COVER SHEET INDICATES SOME CODES FROM THE 2004
 FBC. PLEAS EBE SURE THE PLANS INDICATE THE FOLLOWING
 FOR THIS REVIEWER FOR RELEVANT DESIGN.
  
  
 2007 FBC W/ 2009 SUPPLEMENTS
 2006 NFPA-101
 2008 NFPA-70
 2002 NFPA-728) NOTE: NO FIRE ALARM DEVICES, SYSTEMS
 SHOWN. PLEASE SEE FBC 11-4.28.1,.2 AND .3 FOR MINIMUM
 LOCATIONS, LEVELS AND HEIGHTS FOR ADA COMPLIANCE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  