Date |
Text |
2010-03-11 12:14:22 | BUILDING PLAN REVIEW |
| PERMIT: 10020496 |
| ADD: 1885 OKEECHOBEE RD SUITE 1881 |
| CONT: SETH A FORD |
| TEL: (561)718-7560 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| DESIGN PROFESSIONAL: |
| MCR PROFESSIONAL ENGINEERING, INC. |
| MICHAEL BABER P.E. |
| OFFICE: (561)863-3393 |
| |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| |
| NOTE!!!! THIS COMMENT IS TO MAKE THE DESIGN |
| PROFESSIONAL AND TENANT AWARE OF EXISTING CODE |
| COMPLIANCE ISSUES OF THE EXISTING TENANT CONFIGURATION. |
| AT THIS TIME IT IS NOT CERTAIN THAT THE PROPOSED MEANS |
| OF EGRESS REFLECT THE ORIGINAL PLANS, AND IF THEY WERE, |
| THEY WERE ISSUED IN ERROR, OR IF WORK WAS COMPLETED |
| SINCE THE ISSUED C. O. AND NOT HAVING THE BENEFIT OF |
| PERMIT. |
| |
| ISSUE ONE IS THE OFFICE AREA IS OVER 8,800 SQ FT AND A |
| OCCUPANT LOAD OF 89 OCCUPANTS. |
| FBC-B TABLE 1019.2 WILL ONLY ALLOW AN OCCUPANT LOAD OF |
| 49 WITH A SINGLE EXIT. TWO EXITS ARE REQUIRED AND NOT |
| TRAVELING THROUGH A HIGHER HAZARD OCCUPANCY, STORAGE |
| (FBC-B1014.2.1). THE EXITS THAT LEAD INTO THE WAREHOUSE |
| WOULD NEED TO BE A 2 HR EXIT PASSAGEWAY FROM THE OFFICE |
| OCCUPANCY TO THE WAREHOUSE EXIT. |
| |
| ISSUE TWO IS THERE IS WITHIN THE FENCED IN AREA OF THE |
| WAREHOUSE THERE IS TWO MEANS OF EGRESS WITHIN THIS AREA |
| BUT HEY ARE NOT SEPARATED BY 1/3RD THE DISTANCE |
| (1015.1.2 EXCEPTION 2), THE SECOND ISSUE WITHIN THE |
| FENCED IN AREA WOULD BE THE COMMON PATH OF TRAVEL HAS |
| ALSO BEEN EXCEEDED, SPRINKLERED BUILDING WITH A STORAGE |
| OCCUPANCY ALLOW FOR 100 FT. COMMON PATH OF TRAVEL |
| 1014.3 EXCEPTION 1). |
| |
| THE THIRD AREA OF CONCERN IS THE STORAGE AREA NOT |
| FENCED IN, COMMON PATH OF TRAVEL HAS BEEN EXCEEDED, |
| FBC-B 1014.3 EXCEPTION 1. THE OTHER ISSUE IS HOW ONE |
| DETERMINES IF THE STORAGE AREA IS ONE LARGE ONE OR A |
| OPEN AREA AND A SECOND FENCED IN AREA UNDER LOCK AND |
| KEY. WHEN THE AREA IS CONSIDERED ONE LARGE AREA THERE |
| ARE TWO EXITS BUT YOU WOULD NEED TO TRAVEL THROUGH A |
| LOCKED AREA, THE TOTAL OCCUPANT LOAD OF THIS SPACE |
| WOULD BE 64 REQUIRING TWO DOORS. THE DESIGN TEAM CAN |
| ALLOW THE OCCUPANTS OF THE WAREHOUSE TO TRAVEL THROUGH |
| THE BUSINESS OCCUPANCY TO AN EXIT. BUT THE DOORS THAT |
| LEAD FROM THE OFFICE TO WARE HOUSE WOULD HAVE TO BE |
| REVIEWED FOR SWING IN THE DIRECTION OF TRAVEL, |
| (1008.1.2). |
| |
| COMMENT# 1 UNDER THE CURRENT PLAN REVIEW: |
| |
| 1) THE COVERSHEET CODE DATA INDICATES WARE HOUSE |
| OCCUPANCY AS F-1 AND A OCCUPANT SQ FT OF 500 SQ FT PER |
| PERSON. PLEASE PROVIDE THE TYPE OF MANUFACTURING, FBC-B |
| 306.2 FACTORY- |
| INDUSTRIAL F-1 MODERATE HAZARD. |
| |
| 2) THE OTHER ISSUE IS WITH THE F-1 OCCUPANCY, TABLE |
| 1004.1.1 INDICATES THE OCCUPANCY PER SQ FT WOULD BE 100 |
| SQ FT / PERSON. PLEASE CORRECT. FOR STORAGE/ SHIPPING |
| IT WOULD BE 300 GROSS. |
| |
| 3) PLANS DO NOT PROVIDE A DOOR LEGEND PLEASE PROVIDE TO |
| INDICATE CODE COMPLIANCE WITH FBC-B 715 OPENING |
| PROTECTIVE???S AND TABLE 715.4.NOTE PLANS INDICATE A |
| NEW FIRE RATED DOOR AND JAMB BUT NO OPENING PROTECTION |
| INFORMATION. |
| |
| 4) PLANS INDICATE A NEW MEN???S AND LADIES RESTROOM BUT |
| NO HANDICAPPED FACILITIES. |
| 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS. |
| (1) GENERAL. ALTERATIONS TO EXISTING BUILDINGS AND |
| FACILITIES SHALL COMPLY WITH THE FOLLOWING: |
| (A) NO ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES |
| OR HAS THE EFFECT OF DECREASING ACCESSIBILITY OR |
| USABILITY OF A BUILDING OR FACILITY BELOW THE |
| REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF |
| ALTERATION. |
| 11-4.1.3. (11) TOILET FACILITIES. IF TOILET ROOMS ARE |
| PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM |
| SHALL COMPLY WITH SECTION 11-4.22. |
| 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED, |
| THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL |
| COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE |
| STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING |
| WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES |
| (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING |
| DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D) |
| AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN |
| SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16. IF WATER |
| CLOSETS ARE NOT IN STALLS, THEN AT LEAST ONE SHALL |
| COMPLY WITH SECTION 11-4.16. |
| |
| 5) THE EMPLOYEE LOUNGE INDICATES THE USE OF A SINK, |
| PLEASE PROVIDE DETAILS INDICATING COMPLIANCE WITH: |
| |
| SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED |
| WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH |
| FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| SINK. |
| |
| 6) PLANS WILL ALSO NEED TO PROVIDE COMPLIANCE WITH: |
| INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED |
| IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR FINISH |
| MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN |
| ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED |
| INDEXES. |
| |
| PLEASE INCLUDE A LIFE SAFETY PLAN PROVIDING OCCUPANCY |
| LOADS, EGRESS REQUIREMENTS, EXIT ACCESS, EXIT, EXIT |
| DISCHARGE, EMERGENCY LIGHTING AND EXITS DIRECTIONAL???S |
| AND EXIT SIGNAGE AS WELL AS LOCATION OF FIRE |
| EXTINGUISHERS. WPB ADMINISTRATIVE CODE 106.3.5.1.1(7) & |
| FBC-B 906.1. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| NOTICE. |
| |
| OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| - 5:00 PM. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |