| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| 1. THE NEW PLAN SHOWS 150MPH EXPOSURE B. PLEASE REVISE. |
| |
| 2. PLEASE CLARIFY GIRT SIZING. IF NECESSARY, CIRCLE ON |
| THE CHARTS SUBMITTED. THE FIRST SUBMITTAL INCLUDED A |
| SHEET WHICH PROVIDED GIRT INFORMATION; THIS WAS NOT |
| PROVIDED IN A REVISED FORM FOR EXPOSURE C. HOWEVER, THE |
| LOAD WIDTH APPEARS TOO SHORT (ROUNDING DOWN RATHER THAN |
| ROUNDING UP) AND THE TYPE OF CHAIR RAIL PROPOSED IS NOT |
| CLEAR, ONLY SIZE, BUT NOT ALL SIZES COMPLY. FOR |
| INSTANCE, 4'4" LOAD WITDTH, 7'10" SPAN, 2X3. THE NEW |
| PLAN DOES NOT SPECIFY WHICH 2X3; SMS IS SPECIFIED ON A |
| SHEET FROM THE FIRST SUBMITTAL WHICH SPECIFIES EXPOSURE |
| B. PLEASE REVISE THE PLAN TO INCLUDE THE TYPE OF GIRT |
| PROPOSED. |
| |
| 4'4" LOAD WIDTH - IT APPEARS THAT THIS SHOULD BE 4'5". |
| IT IS NOT CLEAR WHY YOU HAD SPECIFIED A 7'10" SPAN, |
| ISN'T THIS AN 8' SPAN? YOU CANNOT DEDUCT FOR THE |
| MEMBERS, THIS DIMENSION SHOULD GO FROM STRUCTURE/CENTER |
| OF POST TO STRUCTURE/CENTER OF POST. 2X3 SMS REQUIRED, |
| BUT "SMS" WAS NOT SPECIFIED ON ANY OF THE REVISED |
| SHEETS. IT IS NOT CLEAR HOW SPANS HAVE BEEN DETERMINED. |
| |
| FOR THE 3'11"/5' LOAD WIDTH/SPAN, 2X2 SPECIFIED. SMS |
| NOT SPECIFIED, BUT APPEARS TO BE REQUIRED. PLEASE |
| REVISE PLAN TO STATE SPECIFIC SIZE IF ALL DO NOT |
| COMPLY. |
| |
| |
| |
| |
| |
| |
| |
| |