Plan Review Notes
Plan Review Notes For Permit 10020388
Permit Number 10020388
Review Stop P
Sequence Number 1
Notes
Date Text
2010-03-02 07:59:30DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 EXISTING BUILDING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. THE APPLICATION FOR PERMIT INDICATES NO CHANGE OF
 OCCUPANCY. PER CONSTRUCTION DOCUMENTS THE SPACE HAS
 CHANGED FROM R-2 OCCUPANCY TO BUSINESS OCCUPANCY.
 PLEASE INDICATE CHANGE OF OCCUPANCY ON THE APPLICATION.
  
 2. SHT A1.1 DECLARE THE OCCUPANCY CLASSIFICATION PER
 SECTION 302.1. THE ORIGINAL DESIGN FOR THIS SPACE WAS
 R-2 BUT NOW IS INDICATED AS A BUSINESS, (OFFICES).
 (GROUP WORK / LIVE IS NOT AN OCCUPANCY CLASSIFICATION).
  
 3. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE SHOW THE LOCATION OF THE REQUIRED FIXTURE AND
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 WITH ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 4. SUBMIT DETAILS FOR THE KITCHEN SINK AND THE BAR SINK
 SHOWING COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS.
  
 5. SUBMIT A DETAIL FOR THE ACCESSIBLE LAV SHOWING
 COMPLIANCE WITH SECTION 11-4.19 WITH ALL SUBSECTIONS.
  
 6. SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 REQUIRED PIPING FOR THE DRINKING FOUNTAIN AS WELL AS
 THE WATER RISER DIAGRAM FOR THE KITCHEN SINK. SHOW ALL
 PIPE SIZES, TRAPS, VENTS FOR THE SANITARY PIPING AND
 ALL PIPE SIZES, VALVES ETC FOR THE WATER PIPING.
 SECTION 106.3.5.1.3.
  
 7. TOILET ROOM 109. SECTION 1210.2 WALLS WITHIN 2 FEET
 OF THE WATER CLOSET SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE UP TO 4 FEET ABOVE THE FLOOR.
 PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE PANELING
 INDICATING HOW IT MEETS THESE REQUIREMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved