2010-02-24 07:43:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY (CHANGE
 OF USE). THE PLANS ARE TO BE STAMPED AND THE RECEIPT,
 IF FEES ARE OWED, IS TO BE SUBMITTED PRIOR TO PERMIT
 ISSUANCE.
  
 2. PROVIDE SPIRAL STAIR SPECIFICATIONS SHOWING
 COMPLIANCE WITH FBC1009.8.
  
 3. PROVIDE WALL SECTIONS FOR THE WORK AREA AND OFFICE
 PARTITIONS. THE OFFICES APPEAR TO BE OPEN AT THE TOP;
 PLEASE CONFIRM TO SHOW COMPLIANCE WITH FBC505.4,
 OPENNESS FOR MEZZANINES. IT IS NOT CLEAR HOW THE
 PARTITION WALL WILL STRUCTURALLY SUPPORT THE GLASS,
 FBC16. THE DETAIL ON A5.1 SHOWS ATTACHMENT TO DECK
 ABOVE. PLEASE REVISE FLOOR PLAN TO SHOW WALL TYPE WITH
 CORRESPONDING WALL SECTIONS.
  
 4. PROVIDE A STRUCTURAL DETAIL FOR THE TRELLIS.
  
 5. PROVIDE OCCUPANT LOAD FOR THE LOFT AND OFFICE AREAS
 WITH TOTAL SQUARE FEET OF EACH AREA.
  
 6. ADVISORY ONLY, A3.2, INCORRECT JOB ON TITLE BLOCK.
  
 7. HANDRAILS AND GUARDS ARE TO COMPLY WITH FBC1607.7;
 PLEASE REVISE PLAN TO INCLUDE DESIGN CRITERIA.
  
 8. REVISE PLAN TO SHOW COMPLIANCE WITH REQUIREMENT FOR
 VERTICAL ACCESSIBILITY OR SHOW COMPLIANCE WITH ALL
 REQUIREMENTS FOR EXCEPTION IF APPLICABLE,
 FBC11-4.1.6(III)(1)(K).
  
 THIS PERMIT CAN BE ISSUED WITH PROVISO IF ALL OTHER
 DISCIPLINES HAVE PASSED REVIEW AND IMPACT FEE
 REQUIREMENT HAS BEEN SATISFIED.
  
  