Plan Review Notes
Plan Review Notes For Permit 10020380
Permit Number 10020380
Review Stop P
Sequence Number 1
Notes
Date Text
2010-03-08 14:57:37DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 NFPA 99C 1999
  
 1. SHT 1 COMPRESSOR AIR INTAKE SHALL BE FROM OUTSIDE
 THE BUILDING WHEN PRACTICAL OR SHALL BE LOCATED WITHIN
 A ROOM WHERE NO CHEMICAL BASED MATERIAL IS STORED OR
 USED. THE COMPRESSOR IS SHOWN IN A WORKROOM WITH A
 WASHER AND DRYER. THIS IS NOT APPROVED. SECTION
 4-5.1.1.3(E). PLEASE INDICATE WHERE THE AIR INTAKE FOR
 THE COMPRESSOR WILL BE FROM.
  
 2. SHT 1 COMPRESSOR AIR INTAKE SHALL BE LOCATED WHERE
 NO CONTAMINATION FROM VACUUM SYSTEM DISCHARGES OR
 PARTICULATE MATER IS ANTICIPATED. THE COMPRESSOR AIR
 INTAKE SHALL BE TAKEN FROM A SPACE OTHER THAN AN
 OPERATORY AND OTHER THAN THE ROOM OR SPACE IN WHICH
 THERE IS AN OPEN OR SEMI-OPEN DISCHARGE FROM A LEVEL 3
 VACUUM SYSTEM. [SEE 4-5.1.1.3.]
  
 3. SHT 2 REVISION #9 VACUUM VENT TERMINATION OUT THE
 NORTH WALL IS NOT APPROVED PER SECTION 713.6.
  
 4. SHT 3 LIQUIDS FROM A LEVEL 3 VACUUM SYSTEM, PER
 4-5.2.2 SHALL BE DIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM THROUGH AN APPROPRIATELY TRAPPED AND
 VENTED DRAIN. SECTION 4-5.2.1.3. - THE GAS SHALL BE
 DISCHARGED OUT-DOORS IN A MANNER THAT WILL MINIMUZE THE
 HAZARDS OF NOISE AND CONTAMINATION TO THE FACILITY AND
 TO THE ENVIRONMENT. SECTION 4-5.2.1.4. - THE EXHAUST
 SHALL BE LOCATED REMOTE FROM ANY DOOR, WINDOW, AIR
 INTAKE OR OTHER OPENINGS IN THE BUILDING WITH
 PARTICULAR ATTENTION GIVEN TO SEPARATE LEVELS OF INTAKE
 OR DISCHARGE. CARE SHALL BE EXERCISED TO AVOUD
 DISCHARGE LOCATIONS EONTRAINDICATED TO PREVAILING
 WINDS, ADJACENT BUILDINGS, TOPOGRAPHY OR OTHER
 ENFLUENCES. SECTION 4-5.2.1.5.
  
 5. SHT 3 AIR/VACUUM RISER DENIED. NOTE STATES 2" PVC
 VENT TO NORTH EXTERIOR WALL MINIMUM 10' FROM O.A.I. OR
 EXTERIOR DOORS (ABOVE SPA #6 - SEE SHEET #2). PER
 SECTION 713.6 THE VENT SHALL RUN UP ABOVE THE ROOF.
 ALSO THE FUTURE VACUUM INDICATES 'DRAIN TO FLOOR DRAIN
 WHICH IS NOT APPROVED PER SECTION 4-5.2.1.3.
  
 6. SHT 3 WATER RISER DIAGRAM. NOTE 1/2" TO VACUUM SEE
 AIR/VACUUM RISER THIS SHEET, BUT RISER SHOWS WATER TO
 THE COMPRESSOR NOT THE VACUUM. PLEASE CLARIFY. SECTION
 106.1.1.
  
 7. SHT 3 WATER RISER DIAGRAM SHOWS AN RP2 BELOW LAV 1.
 PLEASE INDICATE WHAT MAKE & MODEL AN RP2 IS ON THE
 PLUMBING FIXTURE SCHEDULE AND SUBMIT MANUF
 SPECIFICATIONS FOR THE RP2 TO DETERMINE IF A DRAIN IS
 REQUIRED. SECTION 106.1.2 (MORE INFORMATION REQUIRED).
  
 8. SHT 3 WATER RISER DIAGRAM PLEASE INDICATE ON THE
 PLUMBING FIXTURE SCHEDULE WHAT TYPE OF FILTER THE WSF
 IS. INDICATE MAKE AND MODEL AND SUBMIT MANUF.
 SPECIFICATIONS FOR THE FILTER SHOWING COMPLIANCE WITH
 SECTIONS 611.1 OR 611.3.
  
 9.SHT 3 WASTE RISER DIAGRAM. INDICATE ON THE PLUBMING
 FIXTURE SCHEDULE WHAT AN FSC IS. INDICATE MANUF. MAKE &
 MODEL. SECTION 106.1.2.
  
 10. SHT 3 WASTE RISER DIAGRAM. FS AT FORMER HAIR SINKS
 TO BE CAPPED. NOTE 'A' INDICATES 6' BUT SECTION 704.5
 PROHIBITS DEAD ENDS, (OVER 2 FEET). PLEASE ADJUST NOTE
 TO REFLECT CODE REQUIREMENTS.
  
 11. SHTS SD1 & SD2 THE REQUIRED CLEAR FLOOR SPACE FOR
 THE ACCESSIBLE SHOWERS IS 36" BY 48". THIS IS NOT
 INDICATED. SEE FIGURE 29 IN CHAPTER 11 OF THE FLORIDA
 BUILDING CODE.
  
 12. THE PLAN/PERMIT REVISION FORM INDICATES THE
 INCREASE IN VALUE OF WORK AT ZERO. ALL NEW
 MATERIAL/LABOR & DESIGN FOR THE AIR/VACUUM SYSTEMS,
 WATER PIPING, FILTER, VALVES, SANITARY PIPING, TRAPS,
 FITTINGS SHALL BE INDICATED. PLEASE SHOW VALUATION FOR
 ALL REVISED WORK.
  
 13. A SEPARATE MEDGAS PERMIT IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved