2010-03-08 15:06:43 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| NFPA 99C 1999 |
| |
| 1. SHT 1 COMPRESSOR AIR INTAKE SHALL BE FROM OUTSIDE |
| THE BUILDING WHEN PRACTICAL OR SHALL BE LOCATED WITHIN |
| A ROOM WHERE NO CHEMICAL BASED MATERIAL IS STORED OR |
| USED. THE COMPRESSOR IS SHOWN IN A WORKROOM WITH A |
| WASHER AND DRYER. THIS IS NOT APPROVED. SECTION |
| 4-5.1.1.3(E). PLEASE INDICATE WHERE THE AIR INTAKE FOR |
| THE COMPRESSOR WILL BE FROM. |
| |
| 2. SHT 1 COMPRESSOR AIR INTAKE SHALL BE LOCATED WHERE |
| NO CONTAMINATION FROM VACUUM SYSTEM DISCHARGES OR |
| PARTICULATE MATER IS ANTICIPATED. THE COMPRESSOR AIR |
| INTAKE SHALL BE TAKEN FROM A SPACE OTHER THAN AN |
| OPERATORY AND OTHER THAN THE ROOM OR SPACE IN WHICH |
| THERE IS AN OPEN OR SEMI-OPEN DISCHARGE FROM A LEVEL 3 |
| VACUUM SYSTEM. [SEE 4-5.1.1.3.] |
| |
| 3. SHT 2 REVISION #9 VACUUM VENT TERMINATION OUT THE |
| NORTH WALL IS NOT APPROVED PER SECTION 713.6. |
| |
| 4. SHT 3 LIQUIDS FROM A LEVEL 3 VACUUM SYSTEM, PER |
| 4-5.2.2 SHALL BE DIRECTLY CONNECTED TO THE SANITARY |
| DRAINAGE SYSTEM THROUGH AN APPROPRIATELY TRAPPED AND |
| VENTED DRAIN. SECTION 4-5.2.1.3. - THE GAS SHALL BE |
| DISCHARGED OUT-DOORS IN A MANNER THAT WILL MINIMUZE THE |
| HAZARDS OF NOISE AND CONTAMINATION TO THE FACILITY AND |
| TO THE ENVIRONMENT. SECTION 4-5.2.1.4. - THE EXHAUST |
| SHALL BE LOCATED REMOTE FROM ANY DOOR, WINDOW, AIR |
| INTAKE OR OTHER OPENINGS IN THE BUILDING WITH |
| PARTICULAR ATTENTION GIVEN TO SEPARATE LEVELS OF INTAKE |
| OR DISCHARGE. CARE SHALL BE EXERCISED TO AVOUD |
| DISCHARGE LOCATIONS EONTRAINDICATED TO PREVAILING |
| WINDS, ADJACENT BUILDINGS, TOPOGRAPHY OR OTHER |
| ENFLUENCES. SECTION 4-5.2.1.5. |
| |
| 5. SHT 3 AIR/VACUUM RISER DENIED. NOTE STATES 2" PVC |
| VENT TO NORTH EXTERIOR WALL MINIMUM 10' FROM O.A.I. OR |
| EXTERIOR DOORS (ABOVE SPA #6 - SEE SHEET #2). PER |
| SECTION 713.6 THE VENT SHALL RUN UP ABOVE THE ROOF. |
| ALSO THE FUTURE VACUUM INDICATES 'DRAIN TO FLOOR DRAIN |
| WHICH IS NOT APPROVED PER SECTION 4-5.2.1.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |