 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E1.0 RISER DIAGRAM INDICATES A METER,
 DISCONNECT (FOR PANEL "A") AND PANEL "B", BEING FED
 FROM "A". THE PANEL SCHEDULE IS LABELED PANEL "A". IS
 THE DISCONNECT A COMBINATION DISCONNECT AND PANEL OR IS
 PANEL "B" MISLABELED, CORRELATE SAME. NO FEEDER SHOWN
 TO PANEL "B" FROM PANEL "A" SCHEDULE.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR IS INCORRECT PER
 250.66, MINIMUM SIZE IS #4 CU.
  
 3} THERE IS ONLY ONE SMALL APPLIANCE CIRCUIT SHOWN IN
 THE PANEL SCHEDULE.220.52 SMALL APPLIANCE AND LAUNDRY
 LOADS ??? DWELLING UNIT
 (A) SMALL APPLIANCE CIRCUIT LOAD IN EACH DWELLING UNIT,
 THE LOAD SHALL BE CALCULATED AT 1500 VOLT-AMPERES FOR
 EACH 2-WIRE SMALL-APPLIANCE BRANCH CIRCUIT REQUIRED BY
 210.11(C)(1). WHERE THE LOAD IS SUBDIVIDED THROUGH TWO
 OR MORE FEEDERS, THE CALCULATED LOAD FOR EACH SHALL
 INCLUDE NOT LESS THAN 1500 VOLT-AMPERES FOR EACH 2-WIRE
 SMALL-APPLIANCE BRANCH CIRCUIT. THESE LOADS SHALL BE
 PERMITTED TO BE INCLUDED WITH THE GENERAL LIGHTING LOAD
 AND SUBJECTED TO THE DEMAND FACTORS PROVIDED IN TABLE
 220.42.
  
 4} INDICATE THE LOCATION OF THE METER, MAIN DISCONNECT
 AND PANEL ON THE PLANS.
  
 5} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.INDICATE COMPLIANCE
 ON THE PLANS.
  
 6} PER 210.52 (E)(1) A RECEPTACLE IS REQUIRED AT THE
 FRONT OF THE RESIDENCE.
  