Plan Review Notes
Plan Review Notes For Permit 10020357
Permit Number 10020357
Review Stop B
Sequence Number 1
Notes
Date Text
2010-02-17 10:36:54RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NEED TO PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7 ON SHEET 29 OF NOA SUBMITTED.
 ACCORDING TO GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 09-0224.01 SUBMITTED THE RAS 117 CALCULATIONS NEED TO
 BE SIGNED AND SEALED BY ANY OF THE PROFESSIONALS
 LISTED. SEE LAST PAGE OF NOA SUBMITTED.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $135.23
 FOR UPDATED VALUATION.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712