Plan Review Notes
Plan Review Notes For Permit 10020338
Permit Number 10020338
Review Stop P
Sequence Number 1
Notes
Date Text
2010-02-22 13:47:16DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. A SANITARY ISOMETRIC RISER DIAGRAM IS REQUIRED.
 SECTION 106.3.5.1.3(4)(6)(13). SHOW ALL PIPE SIZES,
 TRAPS, VENTS ETC. SECTIONS 701.1, 901.1 & 1001.1.
  
 2. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED. SECTION
 106.3.5.1.3(3)(10)(13). SHOW ALL PIPES SIZES, VALVES &
 (WHERE REQUIRED BY SECTION 604.9), WATER HAMMER
 ARRESTORS. (DISH WASHER).
  
 3. INDICATE HOW THE SANITARY AND WATER WILL BE ROUTED
 FROM ONE SIDE OF THE ROOM TO THE OTHER. SECTION
 106.1.1.
  
 4. VALUE INDICATED ON THE APPLICATION APPEARS TO BE
 LOW. PLEASE PROVIDE A CONTRACT SIGNED BY THE OWNER.
 VALUE SHALL INCLUDE ALL MATERIALS, LABOR
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved