Date |
Text |
2010-02-22 13:47:16 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 |
| |
| 1. A SANITARY ISOMETRIC RISER DIAGRAM IS REQUIRED. |
| SECTION 106.3.5.1.3(4)(6)(13). SHOW ALL PIPE SIZES, |
| TRAPS, VENTS ETC. SECTIONS 701.1, 901.1 & 1001.1. |
| |
| 2. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED. SECTION |
| 106.3.5.1.3(3)(10)(13). SHOW ALL PIPES SIZES, VALVES & |
| (WHERE REQUIRED BY SECTION 604.9), WATER HAMMER |
| ARRESTORS. (DISH WASHER). |
| |
| 3. INDICATE HOW THE SANITARY AND WATER WILL BE ROUTED |
| FROM ONE SIDE OF THE ROOM TO THE OTHER. SECTION |
| 106.1.1. |
| |
| 4. VALUE INDICATED ON THE APPLICATION APPEARS TO BE |
| LOW. PLEASE PROVIDE A CONTRACT SIGNED BY THE OWNER. |
| VALUE SHALL INCLUDE ALL MATERIALS, LABOR |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |