2010-02-16 16:56:29RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO SEC. R301.2.1.4.3 OF THE 2009 REVISIONS
 TO THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B".
 MODIFIED BITUMEN SYSTEM SELECTED (W-32) DOESN'T RESIST
 THE UPLIFT PRESSURES OF SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE AND NAIL ENHANCING IS NOT ALLOWED.
 NEED TO SELECT SYSTEM THAT MEETS OR EXCEEDS THE
 CALCULATED DESIGN PRESSURES FOR EXPOSURE "C".
  