Plan Review Notes For Permit 10020305 |
Permit Number |
10020305 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-02-22 09:10:19 | BUILDING PLAN REVIEW | | PERMIT: 09060058/ REV: 10020305 | | ADD: 401 N DIXIE HWY | | CONT: THE WEITZ CO. | | TEL: (561) 723-0395 | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | | | ACTION: REVIEWED WITH EXCEPTION | | | | 8X11 SIGNED /SEALED LETTER FROM BRIDGE ENGINEERING FOR | | DOOR PRESSURES STATE ATTORNEY'S OFFICE | | COMPONENTS AND CLADDING | | | | | | | | 1) DOOR NUMBER 8 & 9 REVIEWED, INTERIOR PRESSURE ZONE | | (ZONE # 4) WITH +50PSF, -52PSF | | NOA 09-0324.08 | | | | BUILDING APPROVED WITH EXCEPTION! | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | ASSESSMENT OF RE-INSPECTION FEE(S). | | | | 2) DOOR # 10 IS LOCATED WITHIN A CORNER ZONE (ZONE# 5) | | WITH HIGHER ASSOCIATED PRESSURES +50 PSF, -89PSF, WILL | | REQUIRE A NOA WITH HIGHER ASSOCIATED PRESSURES OR | | ADDITIONAL ENGINEERING. | | | | JIM WITMER C. B. O. | | COMMERCIAL COMBINATION PLAN REVIEW | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | |
|