2010-03-01 15:20:01****PROVISO****
 ****REVISION REQUIRED - REVISE INSTALLATION SCHEDULE OR
 REMOVE OPENING #5 FROM SCOPE****
 ****ISSUED AT CONTRACTOR'S RISK****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. OPENING #5, ANCHOR SPACING FOR BOTTOM TRACK IS 2.49
 ON THE INSTALLATION SCHEDULE PREPARED BY CONTRACTOR,
 BUT THE PRODUCT APPROVAL (PAGE 11) REQUIRES 3" MINIMUM
 ANCHOR SPACING. EITHER REVISE OPENING #5 TO COMPLY WITH
 PRODUCT APPROVAL OR REMOVE FROM SCOPE OF WORK.
  