Plan Review Notes For Permit 10020203 |
Permit Number |
10020203 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-03-23 10:22:36 | NEW SHEETS SUBMITTED, PROVISOS WERE NOT ADDRESSED. | | | | **PROVISO** | | | | 1. PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE | | CAPABILITIES OF RTU AND ROOF EXHAUST FAN. ALSO PROVIDE | | INSTALLATION DETAIL FOR EXHAUST FAN. FBC-M 301.12. | | | | 2. EXHAUST FANS EF-1 AND EF-3 ARE REQUIRED TO PROVIDE | | MINIMUM 100 CFM EACH PER ASHRAE 62.1 TABLE 6-4. | | | | 3. RETURN AIR TRANSFER DUCTS IN TOOMS 102 AND 110 ARE | | TOO SMALL TO MEET THE BALANCED RETURN AIR EXCEPTIONS | | UNDER FBC-M 601.4. | | | | REVISE PLANS AND RESUBMIT ACCORDINGLY PRIOR TO | | INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|