 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING.
  
 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  