Plan Review Notes For Permit 10020203 |
Permit Number |
10020203 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-02-23 10:43:11 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING. | | | | 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE | | INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A | | SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING | | SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD | | DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR | | LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING | | FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN | | USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING | | POWER IDENTIFIED IN ACCORDANCE WITH SECTION | | 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING | | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH | | SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS | | CAN BE DEMONSTRATED ON THE PLANS INDICATING THE | | WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT | | CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES | | ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN | | THE CALCULATIONS. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|