2010-02-10 16:15:06 
 ** DENIED
  
 1) NOTE: PLEASE SEE FBC 13-415.AB.1.4 FOR EXTERIOR
 LIGHTING CONTROLS REQUIRED. IT IS NOT PERMISSIBLE TO
 USE SINGLE POLE SWITCHES AS THE OVER RIDES/CONTROLS.
  
 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE/DENSITY
 CALCULATIONS PER 13-415.AB.2.2.
  
 3) NOTE: PLEASE COORDINATE PLANS. THE SERVICE RISER
 INDICATES A 120/208V SERVICE YET, THE SITE PLANS
 INDICATE PANEL AS 120/240V.
 220,215,230, GIVEN AS GENERAL FOR COORDINATION.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  