Plan Review Notes
Plan Review Notes For Permit 10010504
Permit Number 10010504
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-04 08:44:54*DENIED*
  
  
 1) NOTE: CODE ON PLAN FOR NFPA-70 STILL STATES 2002
 EDITION. THIS WAS REDLINED ON PROVISO SET ISSUED.
 SHOULD BE 2005 NFPA-70 AS THE PERMIT WAS APPLIED FOR
 BEFORE OCTOBER 1ST, 2009.
  
 2) NOTE: FOR CONTRACTOR:
 THE SUBMITTED PLANS HAVE INCREASED THE SCOPE OF WORK TO
 REWIRE THE ENTIRE HOUSE. THE APPLIED INCREASED VALUE IS
 LOW. PLEASE ADJUST.
 FBC108.3
  
 3) NOTE: THE PLANS NOW INDICATE RE-WIRING OF THE
 DWELLING. PLEASE INCLUDE PANEL SCHEDULES FOR MAIN HOUSE
 FOR THE EXISTING PANEL B AND NEW PANEL A. PANELS ARE
 REQUIRED TO SHOW ALL NEW MINIMUM CIRCUITING REQUIRED BY
 CODE AS WELL AS ANY OTHER ADDITIONAL CIRCUITING. PLEASE
 INCLUDE CONDUCTOR SIZES, LOADS AND OVER CURRENT
 PROTECTION FOR ALL BRANCH CIRCUITS AND FEEDERS.
 FOR EXAMPLE: RISER NOW INCLUDES A NEW PANEL *A* HOWEVER
 THERE IS NO LOCATION SHOWING THE OVER CURRENT
 PROTECTION FOR NEW PANEL.
 PLEASE LIST BRANCH CIRCUITS AND LOADS FOR EACH.
 408.4,310.16,240.4, 220 ETC
 ** THE INITIAL PROVISO ISSUED FOR REVISED DETAILED
 PANEL SCHEDULES BEFORE FINAL WERE ALLOWED BASED ON SOME
 RE-WIRE AND EXISTING UNKNOWN CONDITIONS. HOWEVER AS THE
 ENTIRE HOUSE IS BEING BROUGHT UP TO CODE THE PLANS ARE
 REQUIRED TO SHOW ALL MINIMUMS AT THIS TIME.
  
 4) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53. EACH
 SMALL APPLIANCE BRANCH CIRCUIT IS REQUIRED TO BE
 FIGURED AT 1500VA. THIS INCLUDES ALL OVER THE TWO
 MINIMUM.
 FOR EXAMPLE: IF THERE ARE THREE OR FOUR DEDICATED
 CIRCUITS FOR KITCHEN, BREAKFAST AREAS EACH ARE REQUIRED
 TO BE FIGURED AT 1500VA IN ADDITION TO THE TWO MINIMUM.
 ANOTHER EXAMPLE WOULD BE THE DINING ROOM AREA
 RECEPTACLES. IF THESE ARE A SEPARATE CIRCUIT THE 1500VA
 FOR THE DINING ROOM IS IN ADDITION TO THE TWO MINIMUM.
 3 CIRCUITS: 4500VA
 4 CIRCUITS: 6000VA ETC
 * THIS WOULD INCLUDE ANY ADDITIONAL FOR BAR AREA OFF
 FROM KITCHEN AREA AS WELL.
  
  
 5) NOTE: ON THE ORIGINAL PLANS THE PLANS WERE STAMPED
 FOR ALL LOW VOLTAGE TO BE UNDER SEPARATE PERMITS. TO
 DATE NO PERMIT HAS BEEN APPLIED FOR THE LOW VOLTAGE
 SCOPE. HOWEVER INSPECTIONS WERE SCHEDULED FOR ROUGH
 INSPECTIONS OF ELECTRICAL SYSTEMS.
  
 6) NOTE: PLEASE IDENTIFY THE ITEM IN BEDROOM#2 CLOSET.
 PLANS INDICATED AN ELECTRICAL J-BOX HOWEVER IT IS
 UNCLEAR WHAT THIS UNIT IS? THERE IS ANOTHER J-BOX SHOWN
 AT FIRST FLOOR BEHIND STAIRS. PLEASE IDENTIFY.
  
 7) NOTE: PLEASE BE SURE TO LIST ALL OF THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 210.12
  
 8) NOTE: PLEASE BE SURE TO LIST THE REQUIRED DEDICATED
 BATH CIRCUIT(S) PER 210.11C3. ( MUST BE 20AMP #12.
  
 9) NOTE: WHEN ADDING A/C LOADS TO AN EXISTING SERVICE
 LOAD CALCULATIONS ARE REQUIRED TO BE FIGURED PER 220.83
 A.
 DE-RATING OF HEAT LOADS IS NOT PERMITTED.
  
 10) NOTE: WASHER LOAD IS SHOWN AT 1200VA. THIS IS NOT
 PERMITTED PER 220.52B.
  
 11) NOTE: PLEASE SEE 422.13 FOR WATER HEATER LOADS. THE
 LOAD IS CONSIDERED TO BE A CONTINUOUS LOAD THERE-FORE
 THE LOAD IS REQUIRED TO BE FIGURED AT 125%.
  
 12) NOTE: PLEASE SHOW LOCATION OF ROOF-TOP A/C UNIT
 ALONG WITH DISCONNECT AND GFI.
 440.11,440.12,210.63,210.8A3
  
 13) NOTE: ALL RECEPTACLES WITHIN 6FT OF SINKS WHICH ARE
 15/20AMP 120V SHALL BE GFI/GFI PROTECTED. PLEASE SEE
 210.8A7 OF THE 2005 NEC.
  
 ** IT IS IMPORTANT TO KNOW THAT SINCE THERE IS
 INFORMATION NOT YET SUBMITTED THERE MAY BE NEW COMMENTS
 ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  