Notes
Date Text
2010-01-27 10:57:21**PROVISOS**
  
 1. SUPPLY DUCT PENETRATION OF SHAFT SHALL BE PROTECTED
 WITH FIRE DAMPER IN ACCORDANCE WITH FBC-M 607.5.
  
 2. GREASE DUCT SHALL BE CONTINUOUSLY COVERED BY FIRE
 WRAP SYSTEM FROM POINT OF SHAFT PENETRATION TO OUTLET
 TERMINAL IN ACCORDANCE WITH FBC-M 506.3.10.
  
 3. HORIZONTAL GREASE DUCT SHALL BE PROVIDED WITH
 CLEANOUT(S) IN ACCORDANCE WITH FBC-M 506.3.9.
  
 4. SHOW HOW ANGLE SUPPORTS ARE TO BE ATTACHED TO GREASE
 DUCT IN ACCORDANCE WITH FBC-M 506.3.3. ALSO, PROVIDE
 DETAIL FOR SUPPRTS ON VERTICAL SUPPLY DUCT IN
 ACCORDANCE WITH FBC-M 603.3.
  
 5. PROVIDE SUPPLY AND EXHAUST FAN MANUFACTURER'S WIND
 RESISTANCE DATA IN ACCORDANCE WITH FBC-M 301.12.
  
 SUBMIT REVISED PLANS ADDRESSING ALL OF THE ABOVE ISSUES
 PRIOR TO INSPECTION.
  
 SEPARATE FIRE SUPPRESSION PERMIT REQUIRED.
  