Plan Review Notes For Permit 10010440 |
Permit Number |
10010440 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-27 10:57:21 | **PROVISOS** | | | | 1. SUPPLY DUCT PENETRATION OF SHAFT SHALL BE PROTECTED | | WITH FIRE DAMPER IN ACCORDANCE WITH FBC-M 607.5. | | | | 2. GREASE DUCT SHALL BE CONTINUOUSLY COVERED BY FIRE | | WRAP SYSTEM FROM POINT OF SHAFT PENETRATION TO OUTLET | | TERMINAL IN ACCORDANCE WITH FBC-M 506.3.10. | | | | 3. HORIZONTAL GREASE DUCT SHALL BE PROVIDED WITH | | CLEANOUT(S) IN ACCORDANCE WITH FBC-M 506.3.9. | | | | 4. SHOW HOW ANGLE SUPPORTS ARE TO BE ATTACHED TO GREASE | | DUCT IN ACCORDANCE WITH FBC-M 506.3.3. ALSO, PROVIDE | | DETAIL FOR SUPPRTS ON VERTICAL SUPPLY DUCT IN | | ACCORDANCE WITH FBC-M 603.3. | | | | 5. PROVIDE SUPPLY AND EXHAUST FAN MANUFACTURER'S WIND | | RESISTANCE DATA IN ACCORDANCE WITH FBC-M 301.12. | | | | SUBMIT REVISED PLANS ADDRESSING ALL OF THE ABOVE ISSUES | | PRIOR TO INSPECTION. | | | | SEPARATE FIRE SUPPRESSION PERMIT REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|