Date |
Text |
2010-03-16 08:22:46 | CORRECTIONS |
| (COURTESY REVIEW, CONTRACTOR REQUEST) |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| FROM PROVISO LIST, NOT ADDRESSED: |
| |
| 1. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT |
| FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER |
| (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO |
| HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT |
| WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE |
| LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT |
| BE NOTARIZED. |
| |
| 2. TWO SIGNED, SEALED IDENTICAL SETS OF DOCUMENTS |
| REQUIRED FOR PERMIT ISSUANCE. ONE SET IS NOT SEALED, |
| THE OTHER HAS A PHOTOCOPY SIGNATURE. THIS SET HAS BEEN |
| RETAINED. SEE FS471, OR CONTACT FBPE FOR MORE |
| INFORMATION. IF THEY DETERMINE THAT A PHOTOCOPY IS |
| ACCEPTABLE, CONTRARY TO PREVIOUS DISCUSSIONS AND |
| FLORIDA STATUTE, PLEASE ADVISE. |
| |
| NEW COMMENT: |
| |
| 3. INSTALLATION PROPOSED EXCEEDS THE SIZE OF |
| ENGINEERING (ENGINEERING SHOWS A 2'3" PROJECTION, |
| INSTALLATION PROPOSED IS 4'). AS THE PLANS ARE TO BE |
| REVISED BY THE ENGINEER, PLEASE ADDRESS ITEMS 1 AND 2 |
| AT THIS TIME. PLANS ARE TO BE SIGNED, SEALED, DATED |
| ORIGINALS. PLEASE DO NOT SUBMIT UNSEALED PHOTOCOPIES OR |
| PHOTOCOPY SIGNATURES UNLESS SUPPORTED FBPE. |
| |
| 3RD REVIEW COMMENT: |
| |
| CONTRACTOR STATED THAT THE 4' PROJECTION IS INCLUDED IN |
| THE ENGINEERING. PLEASE SEE NOTES, "HEIGHT SHALL BE |
| EQUAL TO OR LARGER THAN PROJECTION". PLEASE REVISE. |
| |
| 4. PLEASE PROVIDE TWO COLLATED IDENTICAL SETS OF PLANS |
| FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE MARKED "VOID" |
| TO AVOID CONFUSION AND DELAYS. |
| |
| |
| |
| |
| |