2010-03-02 16:55:19 | ** PROVISO/REDLINED ** | | | | | | 1) NOTE: PLANS INDICATE 2005 NEC/NFPA-70. REDLINED AND | | STAMPED FOR 2008 NEC. | | | | 2) NOTE: ALL DEVICE LOCATIONS FOR HORN/STROBES, PULL | | STATIONS ETC SHALL BE VERIFIED AND SHOWN ON PLANS. | | THESE LOCATIONS ARE REQUIRED TO COMPLY WITH CHAPTER 11 | | OF THE FBC. | | 11-4.28.1,.2 AND .3. TENANT AREAS WILL BE REQUIRED TO | | SHOW ALL LOCATIONS AND MINIMUM LEVELS. RESPONSE | | MENTIONS DEVICES ALREADY EXISTS HOWEVER BASED ON THE | | SUBMITTED PLANS, NOT ALL ARE SHOWN AS EXISTING. SEE | | AREA 126 FOR EXAMPLE WHICH INDICATES A NEW DEVICE YET | | COMPLIANCE FOR ADA IS NOT SHOWN. THE LOCATIONS OF | | DEVICES IN THIS SAME AREA FOR ADA ARE ALSO NOT MET FOR | | MINIMUM COMPLIANCE. | | | | 3) NOTE: REDLINED PLANS: WIRING METHODS IN NEC 645 ARE | | NOT PERMITTED IN ROOM 205. | | | | 4) NOTE: LOW VOLTAGE SYSTEMS SUCH AS PHONE AND DATA ARE | | REQUIRED TO BE UNDER SEPARATE PERMIT AND PLANS. THESE | | PLANS DO NOT INDICATE LOW VOLTAGE THEREFORE LV LAYOUT | | PLANS WILL BE REQUIRED WHEN SUBMITTING FOR PERMIT. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|