2010-01-28 18:34:53 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 11 |
| |
| 1. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR |
| THE DRINKING FOUNTAIN. (FORWARD APPROACH REQUIRED). |
| SECTION 11-4.15.5. |
| |
| 2. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR |
| THE W/C. SECTION 11-4.16.2. |
| |
| 3. SHT A3.1 DETAIL #10 THE ACCESSIBLE TOILET STALLS DO |
| NOT COMPLY WITH FIGURE 11-30(E). SECTION |
| 11-4.1.6)1)(B). |
| |
| 4. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR |
| THE URINAL. SECTION 11-4.18.3. |
| |
| 5. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR |
| THE LAV. SECTION 11-4.19.3. |
| |
| 6. SHT A3.1 DETAIL #4 SHOW THE KNEE CLEARANCE PER |
| SECTION 11-4.24.3, THE CLEAR FLOOR SPACE PER 11-4.24.5 |
| (CABINET DOORS NOT APPROVED, DELETE) & EXPOSED PIPES & |
| SURFACES PER SECTION 11-4.24.6. |
| |
| 7. SHT M1 SHOW ALL PIPE SIZES. TABLE 710.1(1). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |