2010-01-28 18:34:53DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 1. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR
 THE DRINKING FOUNTAIN. (FORWARD APPROACH REQUIRED).
 SECTION 11-4.15.5.
  
 2. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR
 THE W/C. SECTION 11-4.16.2.
  
 3. SHT A3.1 DETAIL #10 THE ACCESSIBLE TOILET STALLS DO
 NOT COMPLY WITH FIGURE 11-30(E). SECTION
 11-4.1.6)1)(B).
  
 4. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR
 THE URINAL. SECTION 11-4.18.3.
  
 5. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR
 THE LAV. SECTION 11-4.19.3.
  
 6. SHT A3.1 DETAIL #4 SHOW THE KNEE CLEARANCE PER
 SECTION 11-4.24.3, THE CLEAR FLOOR SPACE PER 11-4.24.5
 (CABINET DOORS NOT APPROVED, DELETE) & EXPOSED PIPES &
 SURFACES PER SECTION 11-4.24.6.
  
 7. SHT M1 SHOW ALL PIPE SIZES. TABLE 710.1(1).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  