Plan Review Notes For Permit 10010381 |
Permit Number |
10010381 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-01-26 20:43:34 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. THE BUILDING PLAN REVIEW INDICATES THAT THERE ARE | | REQUIRED RATED TENANT SEPARATION WALLS WHICH ARE NOT | | SHOWN AS SUCH ON PLANS. SOME OF THE AFFECTED WALLS ARE | | SHOWN AS BEING PENETRATED BY DUCTS WITHOUT PROTECTION. | | COORDINATE WITH CORRECTED ARCHITECTURAL PLASN TO SHOW | | THE DUCT PENETRATIONS OF ALL RATED WALLS PROTECTED IN | | ACCORDANCE WITH FBC-M 607.5 AND 607.8. | | | | 2. M1 FLOOR PLAN SHOWS NEW EXHAUST FAN IN NEW PORTION | | OF WOMEN'S RESTROOM. NO INFORMATION WAS PROVIDED | | REGARDING THIS FAN. PROVIDE EQUIPMENT SCHEDULE AND SHOW | | REQUIRED RATINGS AND CFM OF THIS FAN AS WELL AS THE CFM | | OF THE EXISTING EXHAUST SYSTEM TO DEMONSTRATE | | COMPLIANCE WITH FBC-EB 709.1 AND FBC-M TABLE 403.3 | | | | 3. THERE ARE SEVERAL OTHER RECONFIGURED SPACES IN THE | | WORK AREA. PROVIDE SPACE-BY-SPACE VENTILATION | | CALCULATIONS FOR ALL RECONFIGURED SPACES IN ACCORDANCE | | WITH FBC-EB 709.1. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|