2010-01-26 20:43:34REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE BUILDING PLAN REVIEW INDICATES THAT THERE ARE
 REQUIRED RATED TENANT SEPARATION WALLS WHICH ARE NOT
 SHOWN AS SUCH ON PLANS. SOME OF THE AFFECTED WALLS ARE
 SHOWN AS BEING PENETRATED BY DUCTS WITHOUT PROTECTION.
 COORDINATE WITH CORRECTED ARCHITECTURAL PLASN TO SHOW
 THE DUCT PENETRATIONS OF ALL RATED WALLS PROTECTED IN
 ACCORDANCE WITH FBC-M 607.5 AND 607.8.
  
 2. M1 FLOOR PLAN SHOWS NEW EXHAUST FAN IN NEW PORTION
 OF WOMEN'S RESTROOM. NO INFORMATION WAS PROVIDED
 REGARDING THIS FAN. PROVIDE EQUIPMENT SCHEDULE AND SHOW
 REQUIRED RATINGS AND CFM OF THIS FAN AS WELL AS THE CFM
 OF THE EXISTING EXHAUST SYSTEM TO DEMONSTRATE
 COMPLIANCE WITH FBC-EB 709.1 AND FBC-M TABLE 403.3
  
 3. THERE ARE SEVERAL OTHER RECONFIGURED SPACES IN THE
 WORK AREA. PROVIDE SPACE-BY-SPACE VENTILATION
 CALCULATIONS FOR ALL RECONFIGURED SPACES IN ACCORDANCE
 WITH FBC-EB 709.1.
  