Plan Review Notes For Permit 10010381 |
Permit Number |
10010381 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-02-11 10:50:28 | *****DENIED****** | | | | | | 1. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | REFERENCED. | | | | 2. DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL | | WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD OF | | 50 OR MORE, EXCEPT UNDER THE CONDITIONS SPECIFIED IN | | 7.2.1.4. (SEE BUILDING EXAMINER'S COMMENT # THREE). | | | | 3. WHAT ARE THE DASHED LINES BEGINNING FROM THE | | EXTERIOR OF THE DOUBLE EXIT DOORS EXTENDING INTO THE | | LOBBY (ROOM 200) AROUND AND BACK OUT OF THE BUILDING AS | | SHOWN ON LS1.1 SHEET? | | | | 4. AS SHOWN ON SHEET LS1.1, THE NEW PROPOSED WALL WILL | | DENY TENANT SPACE #100 ACCESS TO THE EXISTING FIRE | | ALARM PANEL IN THE SERVER ROOM (ROOM 205) . PLEASE | | EXPLAIN. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|