2010-02-02 14:39:29 | DENIED* |
| |
| |
| 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS SUBMITTED |
| AS REQUIRED PER 13-415.AB.5. |
| PLEASE BE SURE THE FIXTURE LEGEND IS SUBMITTED FOR NEW |
| FIXTURES AND INFORMATION ON OTHERS. |
| PLANS HAVE AN *EX* NEXT TO A COUPLE OF FIXTURES HOWEVER |
| SINCE THE SYMBOL LEGEND DOES NOT INDICATE WHAT THIS IS, |
| IT IS NOT POSSIBLE TO KNOW EXACTLY WHAT THESE ARE. |
| EVEN WHEN NOT MEETING THE DEFINITIONS OF A RENOVATION, |
| PRESCRIPTIVE REQUIREMENTS MUST BE MET. 13-400.B.0.4 |
| |
| 2) NOTE: LIGHTING CONTROLS IN SOME AREAS NOT MEETING |
| FBC 13-415.AB.1.1,.1.2. PLEASE SEE SEPARATE SPACE |
| REQUIREMENTS. ROOMS ARE NOT IDENTIFIED ON ELECTRICAL |
| PLANS SO DESIGNATIONS ON ARCHITECTURAL SHEETS ARE BEING |
| USED. |
| PLEASE SEE ROOMS 100, 206, 211 ETC |
| |
| 3) NOTE: PANEL SCHEDULES AND CIRCUITING TO BE COMPLETE |
| TO SPECIFIC ROOMS AND AREAS IN WHICH THEY FEED. 408.4. |
| ( MAY BE ALPHA OR NUMERIC DESIGNATIONS.) |
| |
| 4) NOTE: PLEASE COORDINATE RISER DIAGRAM OR PANEL |
| INFORMATION FOR NEW PANEL FEED SUBMITTED. |
| RISER INDICATES NEW PANEL AS 60AMP HOWEVER PANEL ON |
| SHEET E-2 STATES THIS AS A 200AMP MCB PANEL? |
| 3/0 AWG WILL NOT FIT INTO 60AMP LUGS. |
| 215.5, 310.16, 240.4 ETC. NO INFORMATION SUBMITTED SO |
| REVIEW OF NEW PANEL FEED CAN NOT BE DONE. |
| |
| 5) NOTE: LOADS ON NEW PANEL ARE ACTUALLY BLANK. THERE |
| IS NO LOAD INFORMATION FOR THIS PANEL OR ON THE |
| PANELS/SERVICE EQUIPMENT WHICH FEEDS NEW PANEL. THIS |
| NEEDS TO BE COMPLETED FOR LOADS ON PANEL K AND A1. |
| PLEASE SEE 220.12,220.14,220.42, 220.44,220.87 ETC |
| PLEASE ALSO SEE 215.3,230.42, 422.13 FOR CONTINUOUS |
| LOADS. |
| ** SECTIONS GIVEN IN GENERAL AS NO LOADS, LOAD |
| CALCULATIONS WERE SUBMITTED FOR PANELS BEING AFFECT. |
| THE LOAD SHOWN FOR SERVICE IS ONLY PART OF THE |
| INFORMATION NEEDED. |
| |
| 6) NOTE: NO INFORMATION SHOWN FOR ADA COMPLIANCE FOR |
| FBC 11-4.1,.2 AND .3. SHOW LOCATIONS, HEIGHTS AND |
| LEVELS OF ALL REQUIRED DEVICES. PLEASE COMPLETE LEGEND |
| FOR MINIMUM REQUIRED DEVICES. |
| |
| 7) NOTE: PLEASE SEE FBC 1006.1.2, NFPA-101 |
| 7.8.1.3,7.9.1.2, .2.2 FOR REQUIRED EMERGENCY EGRESS |
| LIGHTS. NONE SHOWN ON ELECTRICAL PLANS. PLEASE ALSO SEE |
| NEC 700.12F FOR CIRCUITING REQUIREMENTS. |
| A FEW ARE LOCATED ON E-1 HOWEVER NOT ALL REQUIRED. |
| |
| 8) NOTE: PLEASE COMPLETED PLANS FOR LIGHTING AND FAN |
| CONTROLS IN BATHROOM AREAS. SEE NOTES ABOVE WITH |
| RESPECT TO FBC CHAPTER 13 FOR LIGHTING CONTROLS AND |
| ALSO MINIMUM REQUIRED FOR NORMAL AND EMERGENCY EGRESS. |
| |
| 9) NOTE: PER PANEL SCHEDULE ONE OF THE ROOMS WILL BE A |
| NEW SERVER ROOM. IF THIS IS *NOT* AN IT ROOM PER 645.4 |
| (1-5) THEN PLEASE PLACE NOTE ON PLANS WHICH WILL *NOT* |
| PERMIT THE WIRING METHODS PERMITTED IN NEC 645. THE |
| WORDING TO THAT AFFECT MAY BE ADJUSTED. |
| |
| ** FYI: IT PERSONNEL FOR OWNER MAY WANT TO BE CONSULTED |
| WITH DUE THE MORE STRINGENT WIRING METHODS REQUIRED |
| WHEN NOT AN IT ROOM. |
| |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |