Plan Review Notes
Plan Review Notes For Permit 10010381
Permit Number 10010381
Review Stop E
Sequence Number 1
Notes
Date Text
2010-02-02 14:39:29DENIED*
  
  
 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS SUBMITTED
 AS REQUIRED PER 13-415.AB.5.
 PLEASE BE SURE THE FIXTURE LEGEND IS SUBMITTED FOR NEW
 FIXTURES AND INFORMATION ON OTHERS.
 PLANS HAVE AN *EX* NEXT TO A COUPLE OF FIXTURES HOWEVER
 SINCE THE SYMBOL LEGEND DOES NOT INDICATE WHAT THIS IS,
 IT IS NOT POSSIBLE TO KNOW EXACTLY WHAT THESE ARE.
 EVEN WHEN NOT MEETING THE DEFINITIONS OF A RENOVATION,
 PRESCRIPTIVE REQUIREMENTS MUST BE MET. 13-400.B.0.4
  
 2) NOTE: LIGHTING CONTROLS IN SOME AREAS NOT MEETING
 FBC 13-415.AB.1.1,.1.2. PLEASE SEE SEPARATE SPACE
 REQUIREMENTS. ROOMS ARE NOT IDENTIFIED ON ELECTRICAL
 PLANS SO DESIGNATIONS ON ARCHITECTURAL SHEETS ARE BEING
 USED.
 PLEASE SEE ROOMS 100, 206, 211 ETC
  
 3) NOTE: PANEL SCHEDULES AND CIRCUITING TO BE COMPLETE
 TO SPECIFIC ROOMS AND AREAS IN WHICH THEY FEED. 408.4.
 ( MAY BE ALPHA OR NUMERIC DESIGNATIONS.)
  
 4) NOTE: PLEASE COORDINATE RISER DIAGRAM OR PANEL
 INFORMATION FOR NEW PANEL FEED SUBMITTED.
 RISER INDICATES NEW PANEL AS 60AMP HOWEVER PANEL ON
 SHEET E-2 STATES THIS AS A 200AMP MCB PANEL?
 3/0 AWG WILL NOT FIT INTO 60AMP LUGS.
 215.5, 310.16, 240.4 ETC. NO INFORMATION SUBMITTED SO
 REVIEW OF NEW PANEL FEED CAN NOT BE DONE.
  
 5) NOTE: LOADS ON NEW PANEL ARE ACTUALLY BLANK. THERE
 IS NO LOAD INFORMATION FOR THIS PANEL OR ON THE
 PANELS/SERVICE EQUIPMENT WHICH FEEDS NEW PANEL. THIS
 NEEDS TO BE COMPLETED FOR LOADS ON PANEL K AND A1.
 PLEASE SEE 220.12,220.14,220.42, 220.44,220.87 ETC
 PLEASE ALSO SEE 215.3,230.42, 422.13 FOR CONTINUOUS
 LOADS.
 ** SECTIONS GIVEN IN GENERAL AS NO LOADS, LOAD
 CALCULATIONS WERE SUBMITTED FOR PANELS BEING AFFECT.
 THE LOAD SHOWN FOR SERVICE IS ONLY PART OF THE
 INFORMATION NEEDED.
  
 6) NOTE: NO INFORMATION SHOWN FOR ADA COMPLIANCE FOR
 FBC 11-4.1,.2 AND .3. SHOW LOCATIONS, HEIGHTS AND
 LEVELS OF ALL REQUIRED DEVICES. PLEASE COMPLETE LEGEND
 FOR MINIMUM REQUIRED DEVICES.
  
 7) NOTE: PLEASE SEE FBC 1006.1.2, NFPA-101
 7.8.1.3,7.9.1.2, .2.2 FOR REQUIRED EMERGENCY EGRESS
 LIGHTS. NONE SHOWN ON ELECTRICAL PLANS. PLEASE ALSO SEE
 NEC 700.12F FOR CIRCUITING REQUIREMENTS.
 A FEW ARE LOCATED ON E-1 HOWEVER NOT ALL REQUIRED.
  
 8) NOTE: PLEASE COMPLETED PLANS FOR LIGHTING AND FAN
 CONTROLS IN BATHROOM AREAS. SEE NOTES ABOVE WITH
 RESPECT TO FBC CHAPTER 13 FOR LIGHTING CONTROLS AND
 ALSO MINIMUM REQUIRED FOR NORMAL AND EMERGENCY EGRESS.
  
 9) NOTE: PER PANEL SCHEDULE ONE OF THE ROOMS WILL BE A
 NEW SERVER ROOM. IF THIS IS *NOT* AN IT ROOM PER 645.4
 (1-5) THEN PLEASE PLACE NOTE ON PLANS WHICH WILL *NOT*
 PERMIT THE WIRING METHODS PERMITTED IN NEC 645. THE
 WORDING TO THAT AFFECT MAY BE ADJUSTED.
  
 ** FYI: IT PERSONNEL FOR OWNER MAY WANT TO BE CONSULTED
 WITH DUE THE MORE STRINGENT WIRING METHODS REQUIRED
 WHEN NOT AN IT ROOM.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  