2010-01-26 18:51:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. TENANT SEPARATION WALL IS TO MAINTAIN 1 HOUR RATING,
 FBC 708.1(7), 708.3, 708.4. WALL DETAIL W3 IS SPECIFIED
 FOR DOOR INFILL. PLEASE REVISE TO SPECIFY A 1 HOUR WALL
 INFILL DETAIL.
  
 2. PROVIDE OCCUPANT LOAD FOR EACH TENANT SPACE, FBC
 1004.1.
  
 3. DOOR 10 (LOBBY 200) SWINGS AGAINST THE PATH OF EXIT
 TRAVEL, FBC1008.1.2. IT IS NOT CLEAR HOW MANY OCCUPANTS
 THIS EXIT SERVES, BUT PLEASE NOTE THAT THIS IS A
 PRIMARY EXIT AS NOTED ON THE PLAN.
  
 4. ABOVE THE TEXT "LIFE SAFETY PLAN" THERE IS A DASHED
 LINE (INVERTED "U"); PLEASE LABEL AS IT IS UNCLEAR WHAT
 THIS GRAPHIC REPRESENTS.
  
 5. DOOR 11 AT VESTIBULE 207, SHOW 18??? CLEARANCE ON
 PULL SIDE PER FBC FIGURE 11-25.
  
 6. PROVISO ITEM - UL DETAILS (HW AND CL, SEE SHEET
 A3.1) TO BE PROVIDED AT INSPECTION.
  
 7. BATHROOMS ARE A COMMON AREA (TENANCY IN COMMON) AND
 REQUIRE TENANT SEPARATION, FBC 708.1(7), PENETRATIONS
 TO COMPLY WITH FBC712.
  
 8. DETAIL 04 A3.1, BREAK ROOM SINK TO BE ACCESSIBLE,
 FBC 11-4.24.
  
  