Plan Review Notes
Plan Review Notes For Permit 10010378
Permit Number 10010378
Review Stop B
Sequence Number 3
Notes
Date Text
2010-03-31 16:27:45****PROVISO****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DESIGN PRESSURES ARE TOO LOW. SEE FBC R TABLE
 301.2(2) AND FBC R TABLE 301.2(3). BASED ON OPENING
 SIZE, IF OPENING 8 IS IN ZONE 5, 15' BUILDING HEIGHT,
 BETWEEN 20 AND 50SF, -53.24 MINIMUM DESIGN PRESSURE
 REQUIRED. PLEASE PROVIDE BUILDING HEIGHT SO MINIMUM
 DESIGN PRESSURE REQUIREMENTS CAN BE DETERMINED. PLEASE
 CONTACT ME IF YOU NEED ASSISTANCE.
  
 PROVIDE REVISED INSTALLATION SCHEDULE FOR EXPOSURE C AT
 INSPECTION
  