2010-03-08 17:44:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DESIGN PRESSURES ARE TOO LOW. SEE FBC R TABLE
 301.2(2) AND FBC R TABLE 301.2(3). BASED ON OPENING
 SIZE, IF OPENING 8 IS IN ZONE 5, 15' BUILDING HEIGHT,
 BETWEEN 20 AND 50SF, -53.24 MINIMUM DESIGN PRESSURE
 REQUIRED. PLEASE PROVIDE BUILDING HEIGHT SO MINIMUM
 DESIGN PRESSURE REQUIREMENTS CAN BE DETERMINED. PLEASE
 CONTACT ME IF YOU NEED ASSISTANCE.
  
 2. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH ANCHOR CHARTS, SEE SHEET 8; FOR INSTANCE, WALL
 MOUNT 1, CEILING MOUNT 2, ETC.
  
 3. 10" SPACING DOES NOT COMPLY, SEE OPENING 8; THIS
 ANCHOR CANNOT BE USED FOR THIS SPAN AND DEISGN
 PRESSURE, CONCRETE BLOCK SUBSTRATE.
  
 4. ONLY OPENINGS 8-10 ARE ON THE INSTALLATION SCHEDULE.
 IT APPEARS THAT A SHEET IS MISSING.
  
  